Equipment SCCR below the available fault current: the 5 kA rooftop unit on a 22 kA bus

Why packaged HVAC units, control panels and drives often have a short-circuit current rating below the fault current where they are installed, and the fix.

Illustration: four pieces of rooftop equipment compared with 22 kA available fault current. One unit with standard electrical is rated only 5 kA, one has the high-SCCR option, a starter panel has no stated rating and a drive is rated 100 kA with listed fuses.

Illustrative example

The short answer

Equipment short-circuit current rating (SCCR) is the highest fault current the equipment can withstand safely. It must be at least the available fault current at its point of connection. Many rooftop units, condensing units and control panels ship with a standard SCCR of 5 kA, while the available fault current at a 480 V rooftop panel near a large transformer can exceed 20 kA. Compare every marked SCCR with the fault current from the short-circuit study before ordering.

Rule
SCCR at least the available fault current (NEC 110.10, 409.22, 440.10)
Typical standard rating
5 kA on many packaged HVAC units, unless a high-SCCR option is ordered
Fault current comes from
Section 26 05 73 study or the one-line diagram
Common affected equipment
RTUs, condensing units, VFDs, control panels, pump controllers

SCCR is not the same as interrupting rating

Interrupting rating applies to devices that open a fault, such as breakers and fuses. SCCR applies to equipment assemblies, such as an HVAC unit’s control panel, a motor controller or an industrial control panel, and says how much fault current the assembly can withstand while the upstream device clears the fault. Both have to be at least the available fault current. Panelboard interrupting ratings are covered on the 26 24 16 panelboards page.

Where the code requires an SCCR
EquipmentCode reference (2023 NEC)Marked by
Air-conditioning and refrigeration equipment with multiple motors440.4(B), 440.10Equipment nameplate
Industrial control panels409.22, 409.110Panel nameplate, often calculated under UL 508A Supplement SB
Motor control centers430.99MCC nameplate
Industrial machinery670.5Machine nameplate
All equipment110.10General requirement for circuit components

Why fault current is higher than people expect

Worked example: available fault current at a 1,000 kVA transformer
Transformer
1,000 kVA, 480Y/277 V, 5.75 percent impedance
Full-load current = kVA × 1,000 ÷ (480 × 1.732)
1,000,000 ÷ 831 = 1,203 A
Fault current with an infinite utility = FLA ÷ Z
1,203 ÷ 0.0575 = 20.9 kA
Plus motor contribution
Running motors add fault current, often several kA
At a roof panel close to the transformer
Often still above 15 kA

Feeder length and conductor size reduce the fault current downstream. The short-circuit study calculates it at each panel; use its values, not this estimate.

How to check SCCR on submittals

  1. Get the available fault current per panel

    Take it from the short-circuit study in Section 26 05 73 or the one-line diagram. If the study is not done, use the engineer’s preliminary values and flag the equipment for confirmation.

  2. Find the marked SCCR on each submittal

    It is usually in the electrical data table or nameplate drawing. Many packaged units list a standard SCCR and an optional higher one with a specific electrical option.

  3. Read the conditions

    A high SCCR is often valid only with specific upstream protection, such as Class J fuses of a stated size. If the drawings show a breaker, the high rating may not apply.

  4. Compare and order the option

    Where the standard rating is below the available fault current, order the high-SCCR option in the model number. Adding it later in the field is rarely possible.

Example review comment
RTU-1: Submittal page 9 lists SCCR 5 kA, standard electrical. Short-circuit study 26 05 73 lists 22 kA available at panel RP-1. Provide the high-SCCR option (65 kA) and revise the model number, or confirm upstream protection that the listing accepts.

Where to find the rating on a submittal

Manufacturers do not all use the same words. Look for “SCCR”, “short-circuit current rating”, “short circuit rating” or, on transfer switches and some switchgear, “withstand and closing rating”. The value is usually in kA at a stated voltage, sometimes with a list of the protective devices it depends on. On packaged units it often sits in a footnote to the electrical data table or in the options list next to the disconnect choices.

  • If no rating is stated, treat the equipment as unrated and ask for it; do not assume a value.
  • If two ratings are listed, find the option code that selects the higher one and confirm it is in the submitted model number.
  • If the rating depends on fuses, check the fuse class and maximum size against the drawings.

Fixes after the fact

  • Replace the unit’s electrical panel with the manufacturer’s high-SCCR kit, if one exists for the model and can be fitted in the field.
  • Add upstream current-limiting fuses only if the equipment’s listing names that combination; an untested combination does not raise the SCCR.
  • Reduce available fault current with added impedance, such as a reactor or a transformer, which is a design change for the engineer.
  • Each fix costs more than ordering the option at submittal, which is why this belongs in the review.

Where this hides on a typical job

Equipment most often below the fault current
EquipmentWhy
Packaged rooftop units5 kA standard SCCR, high option sold separately
Condensing units and VRF outdoor unitsSame, especially on 208 V and 480 V roof panels
Control panels built by integratorsSCCR calculated under UL 508A, limited by the lowest component
Drives and soft startersHigh ratings tied to specific fuses
Elevator and fire pump controllersRatings tied to specified protection; fire pump controllers have their own listing

Where Cailar fits

What Cailar does

  • Compares a marked SCCR in kA with the available fault current a reviewer confirms for the panel, converting kA and kAIC in code, and flags a rating below it.
  • Marks SCCR as not stated when the equipment data has no value, instead of assuming a rating.

What stays with your reviewer

  • Calculate available fault current. That comes from the short-circuit study.
  • Check the listing conditions, such as required upstream fuses, behind a high SCCR.

Questions and answers

What is SCCR?

Short-circuit current rating is the maximum fault current an equipment assembly can withstand while the upstream protective device clears the fault, without creating a fire or shock hazard. It is marked on the equipment nameplate.

What is the difference between SCCR and AIC?

AIC, the ampere interrupting capacity, applies to devices that interrupt faults, such as breakers and fuses. SCCR applies to equipment assemblies that must withstand a fault while it is cleared, such as control panels and HVAC units.

Why do rooftop units have a 5 kA SCCR?

Many manufacturers list a standard SCCR of 5 kA, which matches the default for components without a tested rating, and offer a higher rating with a specific electrical option. The higher option must be ordered when the available fault current is above 5 kA.

Where do I find the available fault current?

In the short-circuit study, usually Section 26 05 73, or on the one-line diagram. Service equipment in many buildings is also marked with the available fault current under NEC 110.24.

Can upstream fuses raise equipment SCCR?

Only if the equipment’s listing names that combination of fuses. An upstream device that was not tested with the equipment does not raise its rating.

Sources

Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.