Section 23 33 00 Air Duct Accessories: fire and smoke damper ratings that pass inspection
Checking fire, smoke and combination damper submittals under 23 33 00: hourly rating, dynamic closure, UL 555S leakage class, temperature, actuators and access.
Illustrative example
The short answer
Section 23 33 00 covers duct accessories, and its most inspected items are fire, smoke and combination fire/smoke dampers. For each damper the submittal must show a UL 555 fire rating at least equal to what the code requires for the barrier, a dynamic rating where fans keep running, a UL 555S leakage class and temperature rating for smoke dampers, the actuator voltage and fail position, and the manufacturer’s listed installation details.
- MasterFormat division
- 23, HVAC
- Fire dampers
- UL 555; 1½ hour for barriers under 3 hours, 3 hour for 3-hour barriers
- Smoke dampers
- UL 555S; leakage Class I or II, elevated temperature rating
- Coordinate with
- Architectural rated wall plans, Division 28 fire alarm, Division 26 actuator power
What Section 23 33 00 covers
Air duct accessories include volume dampers, backdraft dampers, turning vanes, flexible connectors, duct access doors and the life-safety dampers that protect rated walls, floors and shafts. Most of the section is routine. The fire and smoke dampers are not: they are inspected by the fire marshal, tested at acceptance and periodically under NFPA 80 and NFPA 105, and their installation must follow the manufacturer’s listed instructions exactly.
Fire damper ratings
| Barrier rating | Minimum damper rating | Common mistake |
|---|---|---|
| Less than 3 hours (1 or 2 hour) | 1½ hour | Submitting 3-hour dampers everywhere at extra cost, or 1½ hour in a 3-hour wall |
| 3 hours or more | 3 hour | Using the standard 1½ hour damper in a 3-hour shaft wall |
- Static or dynamic: a static fire damper is rated to close with no airflow, so it is only allowed where fans shut down on alarm. Where fans keep running, the damper must be dynamic, rated to close against a stated airflow and pressure.
- Fusible link or heat-responsive device temperature, commonly 165 °F, higher where normal air temperature is higher.
- Damper type A, B or C (blades in or out of the airstream) affects pressure drop; the spec may require out-of-airstream blades.
- Airflow through the damper
- 2,400 CFM
- Damper free area, 24 × 12 in.
- 2.0 sq ft nominal, about 1.3 sq ft free
- Velocity at the damper
- 2,400 ÷ 1.3 = 1,850 FPM
- Damper dynamic closure rating
- 2,000 FPM at 4 in. wg
- Same opening at 3,000 CFM
- 2,310 FPM, above the rating
Use the free area from the manufacturer’s data, not the nominal size, and the static pressure at the damper location in the system.
Smoke and combination dampers
| Value | Where it comes from | Common problem |
|---|---|---|
| Leakage class under UL 555S | Spec and code | Class II submitted where the spec asks for Class I |
| Elevated temperature rating | Spec | 250 °F where 350 °F is required |
| Airflow and pressure ratings | System design | Velocity at the damper above the rating |
| Actuator voltage | Electrical drawings | 120 V actuators where 24 V circuits are provided |
| Fail position | Smoke control sequence | Fail open where the sequence needs fail closed |
| Position indication | Fire alarm or smoke control panel | No end switches where the panel must confirm position |
Combination fire/smoke dampers must meet both UL 555 and UL 555S. Their actuators are usually powered and monitored by the fire alarm or smoke control system, so the submittal must line up with Division 28 and the electrical drawings. A voltage mismatch here is as costly as on major equipment; see voltage mismatches.
Installation details and access
- The listing covers the damper as installed. The submittal must include the manufacturer’s installation instructions for each barrier type: sleeve gauge, retaining angles, clearances and breakaway connections.
- Access doors are required at every fire and smoke damper for inspection and resetting, and the code requires them to be identified. Include the access door data and size.
- Dampers in shafts, floors and ceilings have different listed details from wall dampers. Check each schedule row’s location.
- Acceptance testing after installation, and periodic testing under NFPA 80 and NFPA 105, depend on the access being usable.
The other accessories in the section
| Accessory | Check |
|---|---|
| Manual volume dampers | Locking quadrant and, above hard ceilings, a remote operator |
| Backdraft and barometric relief dampers | Pressure at which they open, and leakage when closed |
| Flexible duct connectors | Fabric rated for the air temperature and, outdoors, for UV exposure |
| Turning vanes | Single or double wall as the spec requires for the pressure class |
| Duct access doors | Size, insulation and gasketing to match the duct pressure class |
| Duct-mounted sound attenuators | Insertion loss and pressure drop at the scheduled airflow |
Why damper submittals are returned
| Reason | How to avoid it |
|---|---|
| Fire rating below the barrier requirement | Check each wall’s rating on the life-safety plans |
| Static damper where fans keep running | Submit dynamic dampers unless fans shut down on alarm |
| Leakage class or temperature below the spec | Match UL 555S class and temperature to the section |
| Actuator voltage or fail position wrong | Coordinate with the electrical drawings and the smoke control sequence |
| No installation instructions | Include the listed instructions for each barrier type |
| No damper schedule by tag and location | Submit a schedule listing each damper, size, location and rating |
Where Cailar fits
What Cailar does
- Compares each damper’s fire rating in hours, leakage class, temperature and actuator voltage with the requirement for its schedule row, with pages cited.
- Flags a rating lower than required, such as 1½ hours against a 3-hour requirement, and marks a rating that is not stated.
What stays with your reviewer
- Determine barrier ratings from the architectural drawings. The reviewer enters or confirms them.
- Check installation details or field testing.
Questions and answers
What fire damper rating does a 2-hour wall need?
Under the International Building Code, a barrier rated less than 3 hours needs a fire damper rated at least 1½ hours, and a barrier rated 3 hours or more needs a 3-hour damper. Check the edition adopted for the project.
What is the difference between static and dynamic fire dampers?
A static fire damper is tested to close with no airflow and is only allowed where the fans shut down when the fire alarm activates. A dynamic fire damper is tested to close against a stated airflow and pressure and is used where fans may keep running.
What are UL 555S leakage classes?
UL 555S rates smoke dampers by how much air leaks through them when closed. Class I leaks least, then Class II and Class III. Building codes generally require Class II or better, and many specs require Class I.
Do fire dampers need access doors?
Yes. Codes require access to every fire and smoke damper for inspection and resetting, and the access must be identified. The submittal should include the access doors.
Who tests fire and smoke dampers?
Dampers are tested after installation and then periodically, under NFPA 80 for fire dampers and NFPA 105 for smoke dampers. The project spec states who performs the acceptance test.
Sources
Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.
- UL 555, Fire Dampers, and UL 555S, Smoke Dampers
- International Building Code, Chapter 7, ducts and air transfer openings
- NFPA 80 and NFPA 105, inspection and testing of fire and smoke dampers