Section 23 33 00 Air Duct Accessories: fire and smoke damper ratings that pass inspection

Checking fire, smoke and combination damper submittals under 23 33 00: hourly rating, dynamic closure, UL 555S leakage class, temperature, actuators and access.

Illustration: a combination fire smoke damper checked against its rated wall and the electrical drawings. The fire rating and dynamic closure match, but the leakage class is lower than specified and the actuator voltage differs from the power provided.

Illustrative example

The short answer

Section 23 33 00 covers duct accessories, and its most inspected items are fire, smoke and combination fire/smoke dampers. For each damper the submittal must show a UL 555 fire rating at least equal to what the code requires for the barrier, a dynamic rating where fans keep running, a UL 555S leakage class and temperature rating for smoke dampers, the actuator voltage and fail position, and the manufacturer’s listed installation details.

MasterFormat division
23, HVAC
Fire dampers
UL 555; 1½ hour for barriers under 3 hours, 3 hour for 3-hour barriers
Smoke dampers
UL 555S; leakage Class I or II, elevated temperature rating
Coordinate with
Architectural rated wall plans, Division 28 fire alarm, Division 26 actuator power

What Section 23 33 00 covers

Air duct accessories include volume dampers, backdraft dampers, turning vanes, flexible connectors, duct access doors and the life-safety dampers that protect rated walls, floors and shafts. Most of the section is routine. The fire and smoke dampers are not: they are inspected by the fire marshal, tested at acceptance and periodically under NFPA 80 and NFPA 105, and their installation must follow the manufacturer’s listed instructions exactly.

Fire damper ratings

Fire damper rating by barrier
Barrier ratingMinimum damper ratingCommon mistake
Less than 3 hours (1 or 2 hour)1½ hourSubmitting 3-hour dampers everywhere at extra cost, or 1½ hour in a 3-hour wall
3 hours or more3 hourUsing the standard 1½ hour damper in a 3-hour shaft wall
From the International Building Code. Check the edition adopted, and the architectural life-safety plans for each wall’s rating.
  • Static or dynamic: a static fire damper is rated to close with no airflow, so it is only allowed where fans shut down on alarm. Where fans keep running, the damper must be dynamic, rated to close against a stated airflow and pressure.
  • Fusible link or heat-responsive device temperature, commonly 165 °F, higher where normal air temperature is higher.
  • Damper type A, B or C (blades in or out of the airstream) affects pressure drop; the spec may require out-of-airstream blades.
Worked example: is the dynamic rating enough?
Airflow through the damper
2,400 CFM
Damper free area, 24 × 12 in.
2.0 sq ft nominal, about 1.3 sq ft free
Velocity at the damper
2,400 ÷ 1.3 = 1,850 FPM
Damper dynamic closure rating
2,000 FPM at 4 in. wg
Same opening at 3,000 CFM
2,310 FPM, above the rating

Use the free area from the manufacturer’s data, not the nominal size, and the static pressure at the damper location in the system.

Smoke and combination dampers

Smoke damper values to check
ValueWhere it comes fromCommon problem
Leakage class under UL 555SSpec and codeClass II submitted where the spec asks for Class I
Elevated temperature ratingSpec250 °F where 350 °F is required
Airflow and pressure ratingsSystem designVelocity at the damper above the rating
Actuator voltageElectrical drawings120 V actuators where 24 V circuits are provided
Fail positionSmoke control sequenceFail open where the sequence needs fail closed
Position indicationFire alarm or smoke control panelNo end switches where the panel must confirm position

Combination fire/smoke dampers must meet both UL 555 and UL 555S. Their actuators are usually powered and monitored by the fire alarm or smoke control system, so the submittal must line up with Division 28 and the electrical drawings. A voltage mismatch here is as costly as on major equipment; see voltage mismatches.

Installation details and access

  • The listing covers the damper as installed. The submittal must include the manufacturer’s installation instructions for each barrier type: sleeve gauge, retaining angles, clearances and breakaway connections.
  • Access doors are required at every fire and smoke damper for inspection and resetting, and the code requires them to be identified. Include the access door data and size.
  • Dampers in shafts, floors and ceilings have different listed details from wall dampers. Check each schedule row’s location.
  • Acceptance testing after installation, and periodic testing under NFPA 80 and NFPA 105, depend on the access being usable.

The other accessories in the section

Routine accessories and the one thing to check on each
AccessoryCheck
Manual volume dampersLocking quadrant and, above hard ceilings, a remote operator
Backdraft and barometric relief dampersPressure at which they open, and leakage when closed
Flexible duct connectorsFabric rated for the air temperature and, outdoors, for UV exposure
Turning vanesSingle or double wall as the spec requires for the pressure class
Duct access doorsSize, insulation and gasketing to match the duct pressure class
Duct-mounted sound attenuatorsInsertion loss and pressure drop at the scheduled airflow

Why damper submittals are returned

Common rejection reasons
ReasonHow to avoid it
Fire rating below the barrier requirementCheck each wall’s rating on the life-safety plans
Static damper where fans keep runningSubmit dynamic dampers unless fans shut down on alarm
Leakage class or temperature below the specMatch UL 555S class and temperature to the section
Actuator voltage or fail position wrongCoordinate with the electrical drawings and the smoke control sequence
No installation instructionsInclude the listed instructions for each barrier type
No damper schedule by tag and locationSubmit a schedule listing each damper, size, location and rating

Where Cailar fits

What Cailar does

  • Compares each damper’s fire rating in hours, leakage class, temperature and actuator voltage with the requirement for its schedule row, with pages cited.
  • Flags a rating lower than required, such as 1½ hours against a 3-hour requirement, and marks a rating that is not stated.

What stays with your reviewer

  • Determine barrier ratings from the architectural drawings. The reviewer enters or confirms them.
  • Check installation details or field testing.

Questions and answers

What fire damper rating does a 2-hour wall need?

Under the International Building Code, a barrier rated less than 3 hours needs a fire damper rated at least 1½ hours, and a barrier rated 3 hours or more needs a 3-hour damper. Check the edition adopted for the project.

What is the difference between static and dynamic fire dampers?

A static fire damper is tested to close with no airflow and is only allowed where the fans shut down when the fire alarm activates. A dynamic fire damper is tested to close against a stated airflow and pressure and is used where fans may keep running.

What are UL 555S leakage classes?

UL 555S rates smoke dampers by how much air leaks through them when closed. Class I leaks least, then Class II and Class III. Building codes generally require Class II or better, and many specs require Class I.

Do fire dampers need access doors?

Yes. Codes require access to every fire and smoke damper for inspection and resetting, and the access must be identified. The submittal should include the access doors.

Who tests fire and smoke dampers?

Dampers are tested after installation and then periodically, under NFPA 80 for fire dampers and NFPA 105 for smoke dampers. The project spec states who performs the acceptance test.