Section 23 73 13 Modular Indoor Central-Station Air-Handling Units: fan, coil and casing checks

How to review an indoor air handler submittal: total static build-up, fan BHP, coil face velocity, casing leakage, drain pans, sound and shipping splits.

Illustration: an indoor air handler submittal whose fan was selected at a lower total static pressure than the sum of its components, while coil face velocity and casing construction match and casing leakage is not stated.

Illustrative example

The short answer

Section 23 73 13 covers factory-built indoor air handlers assembled from modular sections. Review the submittal by rebuilding the total static pressure from its components, checking the fan and motor at that pressure, checking each coil’s capacity, face velocity, rows and pressure drops, and confirming casing construction and leakage, drain pans, filters, sound power, weights and shipping splits against the schedule and spec.

MasterFormat division
23, HVAC
Main standards
AHRI 430 fans in AHUs, AHRI 410 coils, ASHRAE 62.1 drain pans
Decides most reviews
Fan selection at total static pressure with dirty filters
Coordinate with
23 21 13 piping, 23 09 23 controls, 26 29 23 drives, rigging plan

What Section 23 73 13 covers

Modular indoor air handlers are built from sections chosen for the job: mixing box, filters, coils, fan, humidifier, sound attenuator, access and discharge plenums. Because every unit is configured, the submittal is long, often a drawing set for each unit plus fan, coil and sound printouts. Packaged outdoor air handlers are in 23 74 13 and rooftop units in 23 74 16.13.

Rebuild the total static pressure

The schedule usually gives external static pressure, the resistance of the ductwork outside the unit. The fan must overcome that plus every component inside the unit. Add them up from the submittal’s own component data and compare the sum with the pressure on the fan sheet.

Static pressure build-up for AHU-1 at 20,000 CFM
ComponentPressure drop (in. wg)Note
External static pressure2.00From the schedule
Prefilters, MERV 8, mid-life0.35Halfway between clean and final
Final filters, MERV 13, mid-life0.70Spec says select at mid-life
Cooling coil, wet0.85Wet coil, not dry
Heating coil0.15
Mixing box, dampers, plenums and fan entry0.25From the manufacturer
Total static pressure4.30The fan sheet shows 3.90
Specs vary: some require fan selection at clean filters plus an allowance, some at mid-life, some at final (dirty) filters. Use the one the section states.
Worked example: fan brake horsepower and motor size
Airflow and total static
20,000 CFM at 4.3 in. wg
Fan total efficiency from the fan sheet
65 percent
BHP = CFM × TSP ÷ (6,356 × efficiency)
20,000 × 4.3 ÷ (6,356 × 0.65) = 20.8 BHP
Motor submitted
20 HP
Motor needed
25 HP

At the 3.9 in. wg on the fan sheet, the same fan needed 18.9 BHP and a 20 HP motor looked fine. A larger motor also changes the drive size and the breaker on the electrical drawings.

Coils

Coil values to check
ValueWhy it matters
Total and sensible capacity at scheduled entering airThe coil printout must use the schedule’s entering conditions
Face velocityMany specs cap cooling coils near 500 FPM to keep condensate on the coil
Rows and fins per inchMore rows and fins raise air pressure drop and make cleaning harder
Water flow, entering and leaving temperaturesMust match the chilled or hot water plant design
Water pressure dropFeeds the pump head; see 23 21 23 Hydronic Pumps
Glycol percentageChanges capacity and pressure drop; must match the loop
Tube, fin and header materialCopper and aluminum by default; coated or copper fins where specified
Connection hand and sizeMust match the piping drawings and the mechanical room layout

Casing, drain pans and access

  • Casing construction: wall thickness, double wall, insulation type and thermal break where specified, and panel deflection at the design pressure.
  • Casing leakage: specs often require a maximum leakage at a stated test pressure, sometimes a factory test. Ask for the number; a brochure claim is not enough.
  • Drain pans: ASHRAE 62.1 requires drain pans that slope to the drain so water does not stand, and many specs ask for stainless steel and double slope. The pan must extend under the coil and its headers.
  • Access: access doors on the sections the spec lists, with the swing direction the mechanical room allows.

Sound, weights and shipping splits

Sound power by octave band at the inlet, discharge and casing lets the acoustical consultant check the room. If the spec includes sound data and the submittal does not, it is incomplete. Weights by section and the shipping split locations go to the rigging plan: a unit that ships in one piece may not fit through the mechanical room door or the elevator, and a split adds field labor and a casing seal to inspect.

Motors, drives and fan arrays

Most new air handlers run on variable-frequency drives, and many use fan arrays: several small direct-drive plenum fans in place of one large fan. Arrays change what to check. Each fan has its own motor, so the electrical data lists several smaller motors; the spec may require a stated redundancy, such as full airflow with one fan out of service; and backdraft dampers or blank-off plates may be needed so a stopped fan does not short-circuit air.

  • Confirm who supplies the drive: factory-mounted with the unit, or Division 26 under 26 29 23. The electrical drawings must show the same.
  • Check motors are inverter-duty with shaft grounding or insulated bearings when the spec requires it.
  • For fan arrays, check the redundancy the spec asks for and the airflow with one fan off.
  • Check the motor horsepower against the BHP at the true total static pressure, not at the fan sheet’s figure.

Why air handler submittals are returned

Common rejection reasons
ReasonHow to avoid it
Fan selected below the true total static pressureRebuild the static pressure from the submittal’s own component data
Coil printout at different entering conditionsSelect coils at the schedule’s entering air and water conditions
Face velocity above the spec limitCheck face area against airflow
Casing leakage or deflection not statedRequest the manufacturer’s figures before submitting
No sound dataInclude octave band sound power at inlet, discharge and casing
Weights or splits missingInclude section weights and split drawings for rigging

Where Cailar fits

What Cailar does

  • Reads airflow, static pressure, motor horsepower, coil and casing values from the submittal and compares them with the schedule and spec, converting CFM, in. wg and HP in code.
  • Flags a scheduled value that the submittal does not meet or does not state, citing the page.

What stays with your reviewer

  • Add up the static pressure build-up or recalculate fan BHP. The reviewer does that from the component data.
  • Review sound or rigging.

Questions and answers

What is the difference between external and total static pressure?

External static pressure is the resistance of the duct system outside the unit. Total static pressure adds the pressure drops of everything inside the unit, such as filters, coils and dampers. The fan must be selected at total static pressure.

At what filter condition should an air handler fan be selected?

The specification decides. Some require clean filters plus an allowance, some mid-life, and some final or dirty filters. Selecting at clean filters when the spec says mid-life is a common reason for rejection.

What is a typical maximum coil face velocity?

Many specifications limit cooling coil face velocity to about 500 feet per minute to limit condensate carryover. Check the section for the project’s limit.

How do I calculate fan brake horsepower?

Brake horsepower equals airflow in CFM times total static pressure in inches of water, divided by 6,356 times the fan’s total efficiency. For 20,000 CFM at 4.3 in. wg and 65 percent efficiency it is about 20.8 BHP.

Is a rooftop unit covered by 23 73 13?

No. Section 23 73 13 covers indoor modular air handlers. Packaged outdoor air handlers are usually in 23 74 13 and packaged rooftop air conditioners in 23 74 16.

Sources

Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.