MCA and MOP: minimum circuit ampacity and maximum overcurrent protection
What MCA and MOP mean on an HVAC nameplate, how manufacturers calculate them, how they size the wire and breaker, and what to check on a submittal.
Illustrative example
The short answer
MCA, minimum circuit ampacity, is the smallest conductor ampacity allowed for the equipment’s branch circuit. MOP, maximum overcurrent protection (also written MOCP), is the largest fuse or breaker allowed to protect it. Both are printed on the nameplate of air-conditioning and refrigeration equipment under NEC Article 440, and the electrical design must use them rather than the full-load amps.
- Code basis
- NFPA 70 Article 440, nameplate marking in 440.4(B)
- MCA sizes
- The branch-circuit conductors
- MOP sizes
- The largest fuse or breaker, and its type
- Changes with
- Voltage, electric heat options and power connection kits
Why nameplate amps are not enough
A packaged HVAC unit holds several motors that start and run differently: one or more hermetic compressors, condenser fans and a supply fan, sometimes electric heat. The compressor’s inrush is several times its running current. Sizing the wire and breaker from the sum of running currents would either trip on start or leave the conductors unprotected. The manufacturer therefore works out two numbers for the whole unit and prints them on the nameplate, and NEC 440.4(B) requires that marking on multimotor and combination-load equipment.
| Term | Meaning | Used for |
|---|---|---|
| RLA | Rated load amps of a hermetic compressor, set by the manufacturer | Calculating MCA and MOP |
| LRA | Locked rotor amps, the current at the instant of starting | Starting and voltage-dip studies, disconnect rating |
| FLA | Full-load amps of a fan or other motor | Calculating MCA and MOP |
| MCA | Minimum circuit ampacity for the whole unit | Conductor size |
| MOP or MOCP | Maximum overcurrent protection for the whole unit | Largest fuse or breaker |
How manufacturers calculate MCA and MOP
The method comes from NEC Article 440 and the product safety standard the unit is listed to, UL 1995 or UL 60335-2-40. For a unit with several motors it works out as follows. The nameplate value always governs; the calculation is shown so you can tell when a number on a submittal looks wrong.
- MCA = 125 percent of the largest motor’s current, plus 100 percent of every other motor and load.
- MOP = 225 percent of the largest motor’s current, plus 100 percent of every other motor and load, rounded down to a standard fuse or breaker size.
- Compressors
- 2 × 16.0 RLA
- Condenser fans
- 2 × 1.5 FLA
- Supply fan
- 1 × 6.6 FLA
- MCA
- 1.25 × 16.0 + 16.0 + 3.0 + 6.6 = 45.6 A
- MOP before rounding
- 2.25 × 16.0 + 16.0 + 3.0 + 6.6 = 61.6 A
- MOP on nameplate
- 60 A, the next standard size down
Figures are illustrative. Standard fuse and breaker sizes are listed in NEC 240.6(A).
How MCA and MOP size the circuit
Pick the conductor from MCA
Choose a conductor whose ampacity, at the termination temperature rating, is at least the MCA. For 45.6 A that is 8 AWG copper at 75 °C, rated 50 A. NEC 440.35 requires the conductor ampacity to be at least the marked MCA.
Pick the breaker or fuse from MOP
The device may not exceed the MOP. A 50 A or 60 A device is acceptable in the example; 70 A is not. A device at or close to MOP tolerates the compressor’s starting current best.
Match the device type to the nameplate
If the nameplate says “Max fuse” only, protect the unit with fuses. If it says “Max fuse or HACR breaker”, an HACR-rated breaker is also acceptable. Installing equipment against its listing breaks NEC 110.3(B).
Accept a breaker larger than the wire rating
A 60 A breaker on 8 AWG conductors looks wrong but is allowed. NEC 240.4(G) sends air-conditioning circuits to Article 440, where the device protects against short circuits and the unit’s own protection handles overload.
What to check on a submittal
| Check | Why it matters |
|---|---|
| The MCA and MOP are for the voltage being supplied | A 208–230 V and a 460 V version of the same unit have very different values, see voltage mismatches |
| Panel breaker is not larger than MOP | A larger breaker is a code violation and a common inspection failure |
| Conductors on the electrical drawings meet MCA | Undersized conductors are a safety issue the electrical contractor will price as a change |
| Device type matches the nameplate | Fuse-only equipment cannot be protected by a standard breaker |
| Electric heat or other accessories are included | Units with electric heat often list a separate, higher MCA and MOP with heat |
| Single-point or multi-point power is stated | Without a single-point kit, the unit may need two circuits, each with its own MCA and MOP |
| Values were not changed by a late horsepower or option change | An upsized fan motor raises both values and may push the breaker up a size |
RTU-4: Submittal page 5 lists MOP 60 A at 208–230/3/60. Panel schedule E-601 circuit L1-22 shows a 70 A breaker. Electrical contractor to revise the breaker to 60 A or smaller, HACR type, or engineer to confirm alternate unit data.
Where Cailar fits
What Cailar does
- Reads MCA and MOP from the submittal’s electrical data with the page they came from.
- Compares them with the breaker size a reviewer enters from the panel schedule, and flags a breaker above the MOP or below the MCA.
- Marks MCA or MOP as not stated when the submittal page has no value for them, instead of assuming one.
What stays with your reviewer
- Check conductor sizes, or size them for voltage drop, ambient temperature or conduit fill.
- Replace the electrical engineer’s design or the inspector’s reading of the code.
Questions and answers
Is MOP the same as MOCP?
Yes. MOP (maximum overcurrent protection) and MOCP (maximum overcurrent protective device) are two names for the same nameplate value: the largest fuse or breaker that may protect the equipment.
Can I use a breaker smaller than the MOP?
Yes, as long as it carries the load and the compressor’s starting current without tripping. In practice the breaker is chosen between the MCA and the MOP, at a standard size.
Why can the wire be smaller than the breaker on an HVAC circuit?
NEC 240.4(G) sends air-conditioning and refrigeration circuits to Article 440. There the breaker or fuse protects against short circuits and ground faults, while the unit’s internal protection guards against overload, so the conductor is sized from MCA and the device from MOP.
What does “Max fuse” mean on an HVAC nameplate?
It means the unit is listed for protection by fuses up to that size. If the nameplate does not also say HACR breaker, a circuit breaker is not part of the listing and fuses should be used.
Where do I find MCA and MOP on a submittal?
In the electrical data table of the product data, usually listed by voltage and by option such as electric heat. Confirm you are reading the row for the voltage and options actually being supplied.