Section 23 64 16 Centrifugal Water Chillers: capacity, kW per ton and IPLV on the submittal

Reviewing a centrifugal chiller submittal: capacity at design water temperatures, kW per ton, IPLV or NPLV, fouling factors, pressure drops and starter.

Illustration: a centrifugal chiller submittal where capacity and full-load efficiency look compliant but the selection used a lower evaporator fouling factor than specified and the condenser pressure drop exceeds the limit.

Illustrative example

The short answer

Section 23 64 16 covers water-cooled centrifugal chillers. Check that the selection printout uses the scheduled chilled and condenser water temperatures, flows and fouling factors; that full-load kW per ton and IPLV or NPLV meet the spec and the energy code path; that pressure drops fit the pump selections; and that the starter, electrical data, refrigerant, water box ratings and factory test match the spec.

MasterFormat division
23, HVAC
Rating standard
AHRI 550/590 (I-P)
Efficiency terms
kW per ton at full load, IPLV at standard conditions, NPLV at design
Coordinate with
23 21 23 pumps, 23 65 00 towers, 26 29 23 or unit-mounted drive, ASHRAE 15 machinery room

What Section 23 64 16 covers

Centrifugal chillers are the largest single piece of equipment on most central plants, and usually the longest lead time. Section 23 64 16 covers water-cooled centrifugal machines with fixed or variable speed compressors; screw chillers are in 23 64 26 and scroll chillers in 23 64 23. The submittal is built around a selection printout from the manufacturer’s rating software, and nearly every review question is answered on it.

Read the selection printout first

Values on the printout and where the requirement is
ValueRequirement fromCommon problem
Capacity in tonsChiller scheduleRounded up, or at different water temperatures
Evaporator leaving and entering water temperaturesScheduleSelected at a 10 °F range where the schedule says 12 °F
Evaporator flow in GPMSchedule and pump scheduleFlow does not match the primary pump
Condenser entering and leaving water temperaturesSchedule85 °F entering assumed where the tower is designed for 87 °F
Fouling factorsSpecSelected at a lower fouling factor than specified
Full-load kW per tonSpec, energy codeMeasured at a different capacity or condenser temperature
IPLV or NPLVSpec, energy codeIPLV given where the spec asks for NPLV at design conditions
Evaporator and condenser pressure dropSpec, pump headAbove the spec maximum, so pumps are short of head
Passes and water box arrangementSpec, piping layoutConnections on the wrong end for the mechanical room
Refrigerant and chargeSpecDifferent refrigerant than specified

Fouling factor is the allowance for scale and dirt on the tubes. AHRI 550/590 standard conditions use 0.0001 h·ft²·°F/Btu on the evaporator and 0.00025 on the condenser. A printout selected at a cleaner value shows better capacity and efficiency than the machine will deliver after a few years. If the spec states fouling factors, the printout must use them.

kW per ton, IPLV and NPLV

Full-load efficiency is the power drawn per ton at 100 percent capacity. IPLV, the integrated part load value, weights efficiency at 100, 75, 50 and 25 percent load at AHRI standard conditions. NPLV is the same calculation at the project’s own design conditions. ASHRAE 90.1 sets minimums for both full load and IPLV, with two compliance paths: Path A for machines that run mostly near full load, Path B for machines that run mostly at part load, usually variable speed.

Worked example: what 0.548 kW per ton means
Capacity
500 tons
Full-load efficiency
0.548 kW/ton
Compressor input at full load
500 × 0.548 = 274 kW
COP = 3.517 ÷ kW per ton
3.517 ÷ 0.548 = 6.42
Same machine at 0.580 kW/ton
290 kW, 16 kW more at every full-load hour

One ton is 12,000 Btu/h or 3.517 kW of cooling, which is why COP equals 3.517 divided by kW per ton.

Starter, drive and electrical data

  • Starter type: unit-mounted variable-speed drive, solid-state starter or electromechanical starter. Each has different inrush, footprint and harmonic behavior; the spec chooses.
  • Harmonics: a unit-mounted drive may need a harmonic filter to meet the IEEE 519 limits the spec cites. The submittal should state the expected distortion at the point the spec names.
  • Voltage: large centrifugal chillers may run at 460 V or at medium voltage such as 4,160 V. The voltage must match the one-line diagram; see voltage mismatches.
  • MCA, MOP and the short-circuit current rating of the starter or drive must suit the feeder and the available fault current at the chiller. See MCA and MOP.

Water boxes, refrigerant and testing

  • Water box working pressure, commonly 150 psig, must meet the system pressure at the chiller, which can be higher in tall buildings.
  • Marine water boxes let tubes be cleaned without disconnecting piping; compact boxes do not. The spec usually decides.
  • Tube wall thickness and material: thicker or cupronickel tubes for aggressive condenser water.
  • Refrigerant: low-pressure refrigerants such as R-1233zd(E) and medium-pressure ones such as R-134a or R-513A need different machinery room provisions under ASHRAE 15. Refrigerant monitors, alarms and ventilation are often in another section; confirm they match the refrigerant submitted.
  • Factory performance test: many specs require a test to AHRI 550/590 procedures, sometimes witnessed. The submittal should state the test, the test points and the tolerance.

Why chiller submittals are returned

Common rejection reasons
ReasonHow to avoid it
Selection at different water temperaturesCopy the schedule’s temperatures and flows into the selection
Fouling factor lower than specifiedRerun the selection at the specified values
IPLV where NPLV was requiredReport the value the spec and code path ask for
Pressure drop above the spec maximumChange passes or tube count before submitting
Starter or harmonic data missingInclude the drive data and the harmonic analysis the spec requires
Water box rating below system pressureCheck the pressure at the chiller elevation

Where Cailar fits

What Cailar does

  • Reads capacity, efficiency, flows, pressure drops and electrical data from the selection printout and compares them with the schedule and spec, converting tons, kW, GPM, feet of head and psi in code.
  • Flags a value that misses the requirement, such as a pressure drop above the maximum, and marks values the printout does not state.

What stays with your reviewer

  • Rerun the manufacturer’s selection or calculate IPLV or NPLV.
  • Choose the energy code compliance path. The engineer of record does.

Questions and answers

What is the difference between IPLV and NPLV?

Both weight chiller efficiency at 100, 75, 50 and 25 percent load under AHRI 550/590. IPLV uses AHRI standard rating conditions; NPLV uses the project’s own design conditions, such as a different condenser water temperature.

How do I convert kW per ton to COP?

Divide 3.517 by the kW per ton. One ton of cooling equals 3.517 kW, so a chiller at 0.548 kW per ton has a COP of about 6.42.

What fouling factor should a chiller be selected at?

The one the specification states. AHRI 550/590 standard conditions use 0.0001 h·ft²·°F/Btu for the evaporator and 0.00025 for the condenser. A selection at a cleaner value overstates capacity and efficiency.

What are Path A and Path B in ASHRAE 90.1?

They are two sets of minimum chiller efficiencies. Path A emphasizes full-load efficiency for machines that run mostly near full load; Path B emphasizes part-load efficiency, typical of variable-speed machines. A chiller must meet both the full-load and IPLV values of the path used.

Are screw chillers covered by 23 64 16?

No. Section 23 64 16 is for centrifugal chillers. Rotary-screw water chillers are in 23 64 26 and scroll water chillers in 23 64 23.