Section 23 81 29 Variable Refrigerant Flow Systems: what a VRF submittal must prove

Reviewing a VRF submittal: connected capacity ratio, corrected capacity, piping limits, refrigerant concentration in small rooms and low-ambient heating.

Illustration: a VRF system review where the connected capacity ratio exceeds the specified maximum, the refrigerant concentration in a small office is above the limit, piping length is within limits, and low-ambient heating capacity is not given.

Illustrative example

The short answer

Section 23 81 29 covers variable refrigerant flow systems: outdoor units, indoor units, branch controllers and their controls. A VRF submittal must prove more than unit ratings. Check the connected capacity ratio, capacity corrected for piping length and design temperatures, the piping limits against the layout, the refrigerant concentration in the smallest occupied room, heating capacity at the design low ambient, and the electrical data for both outdoor and indoor units.

MasterFormat division
23, HVAC
Rating standard
AHRI 1230 for VRF multi-split systems
Refrigerant safety
ASHRAE 15 and ASHRAE 34 concentration limits, or the mechanical code
Coordinate with
23 23 00 refrigerant piping, 23 09 23 controls, Division 26 power to every indoor unit

A VRF submittal is a system submittal

A VRF system is one refrigerant circuit serving many indoor units from one outdoor unit or module set. Every indoor unit’s capacity, every pipe length and every room it serves affects the others. That is why reviewing the indoor unit cut sheets one by one misses the problems that matter. The submittal should include, for each system, a piping diagram from the manufacturer’s design software with lengths, heights, pipe sizes, branch fittings and total refrigerant charge.

What a complete VRF package includes
ItemWhy it is needed
System selection report per outdoor unitConnected ratio and corrected capacities
Refrigerant piping diagramLengths, heights and pipe sizes against the limits
Refrigerant charge and room concentration checkSafety limit in the smallest room
Indoor and outdoor unit dataCapacity, airflow, sound, electrical
Branch selector or heat recovery box dataHeat recovery systems only
Controls architectureCentral controller, gateway and building automation interface
Installation manual excerptsClearances, condensate, piping practice

Connected capacity ratio and corrected capacity

The connected capacity ratio is the sum of the indoor units’ nominal capacities divided by the outdoor unit’s nominal capacity. Manufacturers allow a range, often from 50 to 130 percent, and many specs set a tighter maximum. A ratio above 100 percent relies on not every zone peaking at once, which is reasonable in offices and risky in spaces that peak together.

Nominal capacity also falls with long piping, height difference, and design temperatures. The selection report should show capacity corrected for all three. Compare corrected capacity for each indoor unit with the schedule, not nominal.

Refrigerant concentration in small rooms

If the whole system charge leaked into the smallest room it serves, the concentration must stay below the limit set by ASHRAE 15 and ASHRAE 34, or by the mechanical code the jurisdiction adopted. Small offices, hotel rooms and electrical closets on large systems are where this fails.

Worked example: concentration check for an R-410A system
Total system charge
120 lb
Smallest room served
10 × 12 × 9 ft = 1,080 cu ft
Concentration if all charge leaks
120 ÷ 1.08 = 111 lb per 1,000 cu ft
R-410A limit listed in ASHRAE 34
26 lb per 1,000 cu ft
Largest charge this room allows
26 × 1.08 = 28 lb

Options include splitting the system, adding the room to an adjacent space with a permanent opening, or the mitigation measures the code allows. For A2L refrigerants the rules in recent editions of ASHRAE 15 and UL 60335-2-40 differ and add leak detection requirements.

Piping limits

Limits to check against the layout
LimitTypical sourceCommon problem
Total piping lengthManufacturer design guideLayout grew after selection
Longest run, outdoor unit to farthest indoor unitDesign guideRooftop unit serving a far wing
Length after the first branchDesign guideExceeded on long corridors
Height difference, outdoor to indoorDesign guideOutdoor unit at grade serving upper floors
Height difference between indoor unitsDesign guideUnits on several floors on one system
Pipe sizes and branch fittingsSelection reportField substitutions of non-matching fittings
Limits differ by manufacturer and model. Use the design guide for the equipment actually submitted.

Heating, electrical and controls

  • Heating capacity at the design low ambient, and whether the unit is a cold-climate model. Defrost cycles reduce delivered heat; some designs add backup heat.
  • Outdoor unit electrical data, MCA and MOP for the voltage supplied; see MCA and MOP.
  • Indoor units usually need their own single-phase power. Check that the electrical drawings provide it, and the voltage; see voltage mismatches.
  • Condensate pumps for cassettes and ducted units where gravity drainage is not possible.
  • Controls: the central controller and, where the building has a building automation system, the BACnet gateway and the points it exposes.
  • Ventilation: VRF indoor units do not usually provide code ventilation by themselves. The submittal should not claim to unless a dedicated outdoor air system is part of it.

Why VRF submittals are returned

Common rejection reasons
ReasonHow to avoid it
No piping diagram or selection reportInclude the design software output for each system
Connected ratio above the spec maximumRebalance indoor units between systems
Room concentration not checkedCalculate it for the smallest room on every system
Only nominal capacities shownShow corrected capacity for each indoor unit
Heating at design low ambient missingInclude the heating capacity table at the design temperature
Indoor unit power not coordinatedConfirm circuits on the electrical drawings

Where Cailar fits

What Cailar does

  • Compares indoor and outdoor unit capacities, airflow and electrical data with the schedule rows, converting tons, MBH and CFM in code.
  • Flags an indoor unit whose submitted capacity is below its schedule row, or where the submittal gives no value, with the page cited.

What stays with your reviewer

  • Calculate connected ratio, piping limits or refrigerant concentration. Those come from the manufacturer’s design software and the reviewer’s check.
  • Design or resize VRF systems.

Questions and answers

What is the connected capacity ratio in a VRF system?

The sum of the nominal capacities of the indoor units divided by the nominal capacity of the outdoor unit. Manufacturers allow a range, often 50 to 130 percent, and specifications often set a lower maximum.

How do I check refrigerant concentration for a VRF system?

Divide the total system refrigerant charge by the volume of the smallest occupied room the system serves, and compare the result with the limit in ASHRAE 15 and 34 or the adopted mechanical code. For R-410A that limit is listed as 26 lb per 1,000 cubic feet.

What standard rates VRF equipment?

AHRI Standard 1230 covers the performance rating of variable refrigerant flow multi-split air-conditioning and heat pump equipment. Energy codes set minimum efficiencies by reference to it.

Why does VRF capacity change with piping length?

Longer refrigerant piping and greater height differences add pressure drop, which reduces the capacity the outdoor unit can deliver. Manufacturers publish correction factors; the selection report should apply them.

Do VRF indoor units need their own power?

Usually yes. Most indoor units need a single-phase power supply separate from the outdoor unit. The electrical drawings must show circuits for them, and the voltage must match the submitted units.