Section 23 81 29 Variable Refrigerant Flow Systems: what a VRF submittal must prove
Reviewing a VRF submittal: connected capacity ratio, corrected capacity, piping limits, refrigerant concentration in small rooms and low-ambient heating.
Illustrative example
The short answer
Section 23 81 29 covers variable refrigerant flow systems: outdoor units, indoor units, branch controllers and their controls. A VRF submittal must prove more than unit ratings. Check the connected capacity ratio, capacity corrected for piping length and design temperatures, the piping limits against the layout, the refrigerant concentration in the smallest occupied room, heating capacity at the design low ambient, and the electrical data for both outdoor and indoor units.
- MasterFormat division
- 23, HVAC
- Rating standard
- AHRI 1230 for VRF multi-split systems
- Refrigerant safety
- ASHRAE 15 and ASHRAE 34 concentration limits, or the mechanical code
- Coordinate with
- 23 23 00 refrigerant piping, 23 09 23 controls, Division 26 power to every indoor unit
A VRF submittal is a system submittal
A VRF system is one refrigerant circuit serving many indoor units from one outdoor unit or module set. Every indoor unit’s capacity, every pipe length and every room it serves affects the others. That is why reviewing the indoor unit cut sheets one by one misses the problems that matter. The submittal should include, for each system, a piping diagram from the manufacturer’s design software with lengths, heights, pipe sizes, branch fittings and total refrigerant charge.
| Item | Why it is needed |
|---|---|
| System selection report per outdoor unit | Connected ratio and corrected capacities |
| Refrigerant piping diagram | Lengths, heights and pipe sizes against the limits |
| Refrigerant charge and room concentration check | Safety limit in the smallest room |
| Indoor and outdoor unit data | Capacity, airflow, sound, electrical |
| Branch selector or heat recovery box data | Heat recovery systems only |
| Controls architecture | Central controller, gateway and building automation interface |
| Installation manual excerpts | Clearances, condensate, piping practice |
Connected capacity ratio and corrected capacity
The connected capacity ratio is the sum of the indoor units’ nominal capacities divided by the outdoor unit’s nominal capacity. Manufacturers allow a range, often from 50 to 130 percent, and many specs set a tighter maximum. A ratio above 100 percent relies on not every zone peaking at once, which is reasonable in offices and risky in spaces that peak together.
Nominal capacity also falls with long piping, height difference, and design temperatures. The selection report should show capacity corrected for all three. Compare corrected capacity for each indoor unit with the schedule, not nominal.
Refrigerant concentration in small rooms
If the whole system charge leaked into the smallest room it serves, the concentration must stay below the limit set by ASHRAE 15 and ASHRAE 34, or by the mechanical code the jurisdiction adopted. Small offices, hotel rooms and electrical closets on large systems are where this fails.
- Total system charge
- 120 lb
- Smallest room served
- 10 × 12 × 9 ft = 1,080 cu ft
- Concentration if all charge leaks
- 120 ÷ 1.08 = 111 lb per 1,000 cu ft
- R-410A limit listed in ASHRAE 34
- 26 lb per 1,000 cu ft
- Largest charge this room allows
- 26 × 1.08 = 28 lb
Options include splitting the system, adding the room to an adjacent space with a permanent opening, or the mitigation measures the code allows. For A2L refrigerants the rules in recent editions of ASHRAE 15 and UL 60335-2-40 differ and add leak detection requirements.
Piping limits
| Limit | Typical source | Common problem |
|---|---|---|
| Total piping length | Manufacturer design guide | Layout grew after selection |
| Longest run, outdoor unit to farthest indoor unit | Design guide | Rooftop unit serving a far wing |
| Length after the first branch | Design guide | Exceeded on long corridors |
| Height difference, outdoor to indoor | Design guide | Outdoor unit at grade serving upper floors |
| Height difference between indoor units | Design guide | Units on several floors on one system |
| Pipe sizes and branch fittings | Selection report | Field substitutions of non-matching fittings |
Heating, electrical and controls
- Heating capacity at the design low ambient, and whether the unit is a cold-climate model. Defrost cycles reduce delivered heat; some designs add backup heat.
- Outdoor unit electrical data, MCA and MOP for the voltage supplied; see MCA and MOP.
- Indoor units usually need their own single-phase power. Check that the electrical drawings provide it, and the voltage; see voltage mismatches.
- Condensate pumps for cassettes and ducted units where gravity drainage is not possible.
- Controls: the central controller and, where the building has a building automation system, the BACnet gateway and the points it exposes.
- Ventilation: VRF indoor units do not usually provide code ventilation by themselves. The submittal should not claim to unless a dedicated outdoor air system is part of it.
Why VRF submittals are returned
| Reason | How to avoid it |
|---|---|
| No piping diagram or selection report | Include the design software output for each system |
| Connected ratio above the spec maximum | Rebalance indoor units between systems |
| Room concentration not checked | Calculate it for the smallest room on every system |
| Only nominal capacities shown | Show corrected capacity for each indoor unit |
| Heating at design low ambient missing | Include the heating capacity table at the design temperature |
| Indoor unit power not coordinated | Confirm circuits on the electrical drawings |
Where Cailar fits
What Cailar does
- Compares indoor and outdoor unit capacities, airflow and electrical data with the schedule rows, converting tons, MBH and CFM in code.
- Flags an indoor unit whose submitted capacity is below its schedule row, or where the submittal gives no value, with the page cited.
What stays with your reviewer
- Calculate connected ratio, piping limits or refrigerant concentration. Those come from the manufacturer’s design software and the reviewer’s check.
- Design or resize VRF systems.
Questions and answers
What is the connected capacity ratio in a VRF system?
The sum of the nominal capacities of the indoor units divided by the nominal capacity of the outdoor unit. Manufacturers allow a range, often 50 to 130 percent, and specifications often set a lower maximum.
How do I check refrigerant concentration for a VRF system?
Divide the total system refrigerant charge by the volume of the smallest occupied room the system serves, and compare the result with the limit in ASHRAE 15 and 34 or the adopted mechanical code. For R-410A that limit is listed as 26 lb per 1,000 cubic feet.
What standard rates VRF equipment?
AHRI Standard 1230 covers the performance rating of variable refrigerant flow multi-split air-conditioning and heat pump equipment. Energy codes set minimum efficiencies by reference to it.
Why does VRF capacity change with piping length?
Longer refrigerant piping and greater height differences add pressure drop, which reduces the capacity the outdoor unit can deliver. Manufacturers publish correction factors; the selection report should apply them.
Do VRF indoor units need their own power?
Usually yes. Most indoor units need a single-phase power supply separate from the outdoor unit. The electrical drawings must show circuits for them, and the voltage must match the submitted units.