Section 26 29 23 Variable-Frequency Motor Controllers: sizing, harmonics and bypass

Reviewing VFD submittals: size by motor current, not horsepower, SCCR, bypass type, IEEE 519 harmonics, motor lead length and inverter-duty motors.

Illustration: a VFD schedule check where a drive rated for 25 horsepower cannot supply the 37 A full-load current of a six-pole 25 HP pump motor, the SCCR is adequate, and the specified bypass is missing.

Illustrative example

The short answer

Section 26 29 23 covers variable-frequency drives for motors. Check that each drive’s continuous output current covers the motor’s nameplate full-load amps, that input voltage and short-circuit current rating suit the feeder, that the bypass, reactors or harmonic filters match the spec and its IEEE 519 requirement, that motor lead length is within the drive’s limit, and that communication, enclosure and the furnish-and-install split agree with Divisions 23 and 26.

MasterFormat division
26, Electrical
Product standard
UL 61800-5-1 (formerly UL 508C) for drives
Harmonics
IEEE 519 limits at the point the spec names
Coordinate with
23 05 13 motors, 23 09 23 controls, equipment submittals with factory drives

What Section 26 29 23 covers, and who furnishes the drive

Drives can appear in three places on a project: as standalone drives under 26 29 23, as drives furnished with the mechanical equipment and specified in its Division 23 section, or as drives integrated into the motor or pump. Before reviewing the drive itself, confirm which applies to each motor. A pump submittal with an integrated drive and an electrical submittal with a standalone drive for the same pump is a duplicated cost and a coordination failure.

Common furnish and install splits
ArrangementWho furnishesWho installs and wiresWatch for
Standalone driveElectrical contractor under 26 29 23Electrical contractorControl wiring and BACnet points by the controls contractor
Drive furnished with equipmentMechanical contractor via the manufacturerElectrical contractor, unless factory-mountedDrive must still meet 26 29 23 requirements the spec cites
Integrated drive on motor or pumpMechanical contractorElectrical contractor wires the inputHarmonic and disconnect requirements still apply

Size the drive by current, not horsepower

Drives are sold by horsepower but rated by continuous output current. Horsepower tables assume a standard four-pole motor. Slower motors, older motors and some pump and fan motors draw more current at the same horsepower, and the drive must supply the motor’s actual nameplate full-load amps. Use the motor data from the approved equipment submittal.

Worked example: a 25 HP drive on a 25 HP motor that does not fit
NEC Table 430.250, 25 HP at 460 V
34 A
Pump motor nameplate, 6-pole, 1,180 RPM
37 A
Drive “25 HP” normal-duty continuous output
34 A
Drive “30 HP” normal-duty continuous output
40 A

Normal duty (variable torque) ratings suit fans and centrifugal pumps. Constant torque loads need the heavy-duty rating, usually one size smaller for the same frame.

Harmonics and IEEE 519

Drives draw non-sinusoidal current that distorts the building’s voltage. Many specs require compliance with IEEE 519 at a stated point of common coupling, often the utility service. IEEE 519-2014 limits total demand distortion according to the ratio of available short-circuit current to maximum load current at that point.

IEEE 519-2014 current distortion limits, systems up to 69 kV
Short-circuit ratio Isc/ILMaximum total demand distortion
Below 205 percent
20 to 508 percent
50 to 10012 percent
100 to 1,00015 percent
Above 1,00020 percent
Limits apply at the point of common coupling the spec names. A drive’s own distortion figure is not the same as compliance at that point; the spec may require a harmonic analysis.
  • Input line reactors or DC link chokes, typically 3 to 5 percent impedance, reduce distortion and protect the drive.
  • Passive harmonic filters or active front-end drives are used where the analysis shows reactors are not enough.
  • The submittal should state which is supplied for each drive and include the analysis if the spec requires one.

Ratings, bypass and the motor side

Drive values to check
ValueCommon problem
Input voltage and phase208 V drive on a 480 V circuit; see voltage mismatches
Short-circuit current ratingSCCR only valid with specific upstream fuses that are not on the drawings
BypassNo bypass where the spec requires one, or two-contactor where three-contactor is required
Input disconnectMissing where the drive is out of sight of the panel
EnclosureNEMA 1 drive in a NEMA 12 or rooftop location
Motor lead lengthDrive to motor distance above the drive’s limit without an output filter
Ambient temperature and altitudeDrive in a hot mechanical room or high-altitude site without derating
CommunicationBACnet MS/TP card missing where controls need it

On the motor side, drive-fed motors should be inverter-duty to NEMA MG 1 Part 31, and many specs require shaft grounding rings or insulated bearings to prevent bearing damage from induced shaft currents. Those requirements usually sit in Section 23 05 13, so check the motor submittal and the drive submittal together.

Why VFD submittals are returned

Common rejection reasons
ReasonHow to avoid it
Drive sized by horsepower below motor FLASize each drive from the approved motor nameplate current
Bypass type differs from the specMatch the bypass arrangement in 26 29 23
No harmonic data or analysisInclude reactors, filters and the analysis the spec requires
SCCR conditions not metShow the required upstream protection on the drawings
Duplicate drives with integrated-drive equipmentConfirm the furnish split for every motor
Lead length exceeds the limitAdd an output filter or relocate the drive

Where Cailar fits

What Cailar does

  • Compares drive input voltage, horsepower, output current and SCCR with the requirement and with the motor data on the approved equipment submittal, converting HP, A and kA in code.
  • Flags a drive whose stated rating is below the requirement, and marks ratings the drive data does not state.

What stays with your reviewer

  • Run harmonic analyses or check IEEE 519 compliance at the point of common coupling.
  • Decide the furnish-and-install split between trades.

Questions and answers

Should a VFD be sized by horsepower or current?

By current. The drive’s continuous output current must be at least the motor’s nameplate full-load amps. Horsepower ratings assume a standard four-pole motor, and slower or older motors can draw more current than the drive’s horsepower suggests.

What does IEEE 519 require for drives?

IEEE 519 sets limits on voltage and current distortion at the point of common coupling. For current, total demand distortion is limited from 5 to 20 percent depending on the ratio of short-circuit current to load current. Specs state where compliance is measured.

What is a three-contactor bypass?

A bypass with input and output contactors around the drive plus a bypass contactor, so the motor can run across the line while the drive is isolated for service. A two-contactor bypass lacks the drive input contactor.

Do drive-fed motors need to be inverter-duty?

Many specifications require it. NEMA MG 1 Part 31 defines motors for inverter use, and shaft grounding or insulated bearings are often required to prevent bearing damage. These requirements are usually in Section 23 05 13.

What is normal duty versus heavy duty on a VFD?

Normal duty, or variable torque, ratings suit fans and centrifugal pumps, whose torque falls with speed. Heavy duty, or constant torque, ratings suit conveyors and positive displacement loads and allow a short overload. The same drive frame has a lower heavy-duty rating.

Sources

Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.