Section 26 29 23 Variable-Frequency Motor Controllers: sizing, harmonics and bypass
Reviewing VFD submittals: size by motor current, not horsepower, SCCR, bypass type, IEEE 519 harmonics, motor lead length and inverter-duty motors.
Illustrative example
The short answer
Section 26 29 23 covers variable-frequency drives for motors. Check that each drive’s continuous output current covers the motor’s nameplate full-load amps, that input voltage and short-circuit current rating suit the feeder, that the bypass, reactors or harmonic filters match the spec and its IEEE 519 requirement, that motor lead length is within the drive’s limit, and that communication, enclosure and the furnish-and-install split agree with Divisions 23 and 26.
- MasterFormat division
- 26, Electrical
- Product standard
- UL 61800-5-1 (formerly UL 508C) for drives
- Harmonics
- IEEE 519 limits at the point the spec names
- Coordinate with
- 23 05 13 motors, 23 09 23 controls, equipment submittals with factory drives
What Section 26 29 23 covers, and who furnishes the drive
Drives can appear in three places on a project: as standalone drives under 26 29 23, as drives furnished with the mechanical equipment and specified in its Division 23 section, or as drives integrated into the motor or pump. Before reviewing the drive itself, confirm which applies to each motor. A pump submittal with an integrated drive and an electrical submittal with a standalone drive for the same pump is a duplicated cost and a coordination failure.
| Arrangement | Who furnishes | Who installs and wires | Watch for |
|---|---|---|---|
| Standalone drive | Electrical contractor under 26 29 23 | Electrical contractor | Control wiring and BACnet points by the controls contractor |
| Drive furnished with equipment | Mechanical contractor via the manufacturer | Electrical contractor, unless factory-mounted | Drive must still meet 26 29 23 requirements the spec cites |
| Integrated drive on motor or pump | Mechanical contractor | Electrical contractor wires the input | Harmonic and disconnect requirements still apply |
Size the drive by current, not horsepower
Drives are sold by horsepower but rated by continuous output current. Horsepower tables assume a standard four-pole motor. Slower motors, older motors and some pump and fan motors draw more current at the same horsepower, and the drive must supply the motor’s actual nameplate full-load amps. Use the motor data from the approved equipment submittal.
- NEC Table 430.250, 25 HP at 460 V
- 34 A
- Pump motor nameplate, 6-pole, 1,180 RPM
- 37 A
- Drive “25 HP” normal-duty continuous output
- 34 A
- Drive “30 HP” normal-duty continuous output
- 40 A
Normal duty (variable torque) ratings suit fans and centrifugal pumps. Constant torque loads need the heavy-duty rating, usually one size smaller for the same frame.
Harmonics and IEEE 519
Drives draw non-sinusoidal current that distorts the building’s voltage. Many specs require compliance with IEEE 519 at a stated point of common coupling, often the utility service. IEEE 519-2014 limits total demand distortion according to the ratio of available short-circuit current to maximum load current at that point.
| Short-circuit ratio Isc/IL | Maximum total demand distortion |
|---|---|
| Below 20 | 5 percent |
| 20 to 50 | 8 percent |
| 50 to 100 | 12 percent |
| 100 to 1,000 | 15 percent |
| Above 1,000 | 20 percent |
- Input line reactors or DC link chokes, typically 3 to 5 percent impedance, reduce distortion and protect the drive.
- Passive harmonic filters or active front-end drives are used where the analysis shows reactors are not enough.
- The submittal should state which is supplied for each drive and include the analysis if the spec requires one.
Ratings, bypass and the motor side
| Value | Common problem |
|---|---|
| Input voltage and phase | 208 V drive on a 480 V circuit; see voltage mismatches |
| Short-circuit current rating | SCCR only valid with specific upstream fuses that are not on the drawings |
| Bypass | No bypass where the spec requires one, or two-contactor where three-contactor is required |
| Input disconnect | Missing where the drive is out of sight of the panel |
| Enclosure | NEMA 1 drive in a NEMA 12 or rooftop location |
| Motor lead length | Drive to motor distance above the drive’s limit without an output filter |
| Ambient temperature and altitude | Drive in a hot mechanical room or high-altitude site without derating |
| Communication | BACnet MS/TP card missing where controls need it |
On the motor side, drive-fed motors should be inverter-duty to NEMA MG 1 Part 31, and many specs require shaft grounding rings or insulated bearings to prevent bearing damage from induced shaft currents. Those requirements usually sit in Section 23 05 13, so check the motor submittal and the drive submittal together.
Why VFD submittals are returned
| Reason | How to avoid it |
|---|---|
| Drive sized by horsepower below motor FLA | Size each drive from the approved motor nameplate current |
| Bypass type differs from the spec | Match the bypass arrangement in 26 29 23 |
| No harmonic data or analysis | Include reactors, filters and the analysis the spec requires |
| SCCR conditions not met | Show the required upstream protection on the drawings |
| Duplicate drives with integrated-drive equipment | Confirm the furnish split for every motor |
| Lead length exceeds the limit | Add an output filter or relocate the drive |
Where Cailar fits
What Cailar does
- Compares drive input voltage, horsepower, output current and SCCR with the requirement and with the motor data on the approved equipment submittal, converting HP, A and kA in code.
- Flags a drive whose stated rating is below the requirement, and marks ratings the drive data does not state.
What stays with your reviewer
- Run harmonic analyses or check IEEE 519 compliance at the point of common coupling.
- Decide the furnish-and-install split between trades.
Questions and answers
Should a VFD be sized by horsepower or current?
By current. The drive’s continuous output current must be at least the motor’s nameplate full-load amps. Horsepower ratings assume a standard four-pole motor, and slower or older motors can draw more current than the drive’s horsepower suggests.
What does IEEE 519 require for drives?
IEEE 519 sets limits on voltage and current distortion at the point of common coupling. For current, total demand distortion is limited from 5 to 20 percent depending on the ratio of short-circuit current to load current. Specs state where compliance is measured.
What is a three-contactor bypass?
A bypass with input and output contactors around the drive plus a bypass contactor, so the motor can run across the line while the drive is isolated for service. A two-contactor bypass lacks the drive input contactor.
Do drive-fed motors need to be inverter-duty?
Many specifications require it. NEMA MG 1 Part 31 defines motors for inverter use, and shaft grounding or insulated bearings are often required to prevent bearing damage. These requirements are usually in Section 23 05 13.
What is normal duty versus heavy duty on a VFD?
Normal duty, or variable torque, ratings suit fans and centrifugal pumps, whose torque falls with speed. Heavy duty, or constant torque, ratings suit conveyors and positive displacement loads and allow a short overload. The same drive frame has a lower heavy-duty rating.
Sources
Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.
- IEEE 519-2014, Recommended Practice and Requirements for Harmonic Control in Electric Power Systems
- UL 61800-5-1, adjustable speed electrical power drive systems
- NEMA MG 1, Part 31, definite-purpose inverter-fed motors
- NFPA 70, National Electrical Code, Article 430 and Table 430.250