Section 26 32 13 Engine Generators: ratings, derates and NFPA 110 on the submittal

Reviewing a generator submittal: standby or prime rating, kW at site altitude, motor starting, NFPA 110 level and type, emissions tier, tank and sound.

Illustration: a generator submittal whose sea-level rating meets the load but whose rating after altitude derate falls short, with NFPA 110 classification and sound matching and voltage dip not stated.

Illustrative example

The short answer

Section 26 32 13 covers diesel and gaseous engine generators for emergency, legally required and optional standby power. Check the rating type and kW at 0.8 power factor after the manufacturer’s derates for site altitude and temperature, the voltage dip on the largest motor step, the NFPA 110 level, type and class, the EPA emissions tier for the application, the fuel tank, enclosure sound level, and the accessories NFPA 110 requires.

MasterFormat division
26, Electrical
Ratings
Standby, prime and continuous, as defined in ISO 8528-1
Emergency systems
NFPA 110 level, type (start time) and class (run time)
Coordinate with
26 36 00 transfer switches, structural pad, fuel and air permits

What Section 26 32 13 covers

Engine generators provide power when the utility fails. The same section often covers emergency systems under NEC Article 700, legally required standby under Article 701 and optional standby under Article 702, and the requirements differ. The submittal is long: engine and alternator data, derate tables, transient response, emissions certificates, fuel tank, enclosure, controller and accessories. Transfer switches are usually a separate submittal under 26 36 00.

Rating type and site derates

Generator rating types under ISO 8528-1
RatingIntended useWhat to watch
Emergency standbyUtility outages, limited hours a year, variable loadMost emergency and standby projects use this
PrimeUnlimited hours at variable load, where there is no utilityLower kW than standby for the same set
ContinuousConstant load, unlimited hoursLowest kW figure

Engine output falls with altitude and high intake air temperature. Each manufacturer publishes derate tables for each engine. The submittal must show the kW at the project’s elevation and design ambient, not only at sea level and 77 °F.

Worked example: altitude derate on a 500 kW set
Standby rating at sea level
500 kW at 0.8 PF = 625 kVA
Site elevation
5,000 ft
Manufacturer derate for this engine (example)
3 percent per 1,000 ft above 3,000 ft = 6 percent
Rating at site
500 × 0.94 = 470 kW
Required by the load calculation
480 kW

The derate rate shown is an example only; use the table for the engine submitted. Kilowatts are real power; kVA is kW divided by power factor.

Motor starting and voltage dip

A generator has far less short-circuit capacity than the utility, so a large motor starting across the line pulls the voltage down. Specs set a maximum voltage dip, often 15 to 20 percent, and the load is usually added in steps through transfer switches. The submittal should include the manufacturer’s sizing report showing each step, the starting kVA and the resulting dip.

  • Motors on drives draw much less starting current but add harmonic distortion that some alternators handle poorly.
  • Fire pumps on generator power have their own NFPA 20 requirements for the set’s capacity to start and run them.
  • Elevator regeneration can push power back into the generator; the spec may require a load bank or a regenerative power sink.

NFPA 110, emissions and the fuel tank

What NFPA 110 terms mean on the submittal
TermMeaningExample
LevelLevel 1 where failure could cost life; Level 2 where it is less criticalHospitals and egress lighting are Level 1
TypeMaximum seconds to restore powerType 10 means 10 seconds
ClassMinimum hours at rated load without refuelingClass 48 means 48 hours
  • Emissions: under EPA rules, stationary engines used only for emergency service are generally certified to a lower tier than non-emergency engines, which may need Tier 4. Air districts may add their own limits. The certificate must cover the engine model and the use.
  • Fuel tank: a sub-base tank listed to UL 142 or UL 2085, sized for the NFPA 110 class at the engine’s fuel consumption, with the leak detection and venting the fire code requires.
  • Accessories NFPA 110 requires for Level 1, such as the remote annunciator, battery charger alarms and engine heater, should all be listed.

Alternator, enclosure and electrical

Other values to check
ValueCommon problem
Output voltage and connectionAlternator reconnectable but shipped for the wrong voltage; see voltage mismatches
Alternator temperature rise125 °C rise where the spec asks for 105 °C
Output circuit breakersNumber and ratings differ from the one-line
Load bank connectionMissing where the spec requires one for testing
Enclosure sound levelRated at a different distance than the spec, such as 7 m instead of 23 ft
Enclosure wind and seismic ratingNot stated for the site
Auxiliary powerBlock heater, battery charger and enclosure power not on the electrical drawings

Where generator packages fail review

Generator review failures and prevention
ProblemPrevention
Sea-level rating shownInclude the derate at site altitude and design temperature
No motor starting or voltage dip reportInclude the sizing report with each load step
Emissions tier wrong for the useMatch the certificate to emergency or non-emergency use
Tank too small for the NFPA 110 classSize from fuel consumption at full load
Sound at the wrong distanceReport at the distance the spec states
Required Level 1 accessories missingCheck the NFPA 110 list against the submittal

Where Cailar fits

What Cailar does

  • Compares kW, voltage, run time, sound level and other stated values with the requirement, converting kW and hours in code.
  • Flags a value below the requirement and marks values the submittal does not state, such as the voltage dip on the largest step.

What stays with your reviewer

  • Size generators, apply derate tables or calculate voltage dip.
  • Confirm emissions certification or air permits.

Questions and answers

What is the difference between standby and prime generator ratings?

Under ISO 8528-1, a standby rating is for emergency use during utility outages for limited hours a year at variable load. A prime rating is for unlimited hours at variable load where there is no utility, and is lower than the standby rating for the same set.

What does NFPA 110 Level 1, Type 10, Class 48 mean?

Level 1 means failure could result in loss of life or serious injury. Type 10 means power must be restored within 10 seconds. Class 48 means the system must run at least 48 hours at rated load without refueling.

Why does generator capacity fall at high altitude?

Thinner air holds less oxygen, so the engine produces less power. High intake air temperature has a similar effect. Manufacturers publish derate tables, and the submittal should show the rating at the project’s elevation and design temperature.

How do I convert generator kW to kVA?

Divide kW by the power factor. Generators are usually rated at 0.8 power factor, so a 500 kW set is 625 kVA.

Does an emergency generator need Tier 4 emissions?

Generally not under EPA rules when the engine is used only for emergency service, but non-emergency use can require Tier 4, and local air districts may set stricter limits. The spec and the permit decide.

Sources

Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.