Airflow below schedule at the stated static pressure: the shortfall TAB finds too late

Why a unit showing the scheduled CFM can still fall short: accessory static left out, altitude, wet coils, and the fan law cost of fixing it later.

Illustration: a rooftop unit fan selected for the scheduled airflow at a lower static pressure than scheduled because accessory pressure drops were left out; at the scheduled pressure the fan delivers less air.

Illustrative example

The short answer

Airflow below schedule means the fan cannot move the scheduled CFM against the scheduled external static pressure once every accessory is in the airstream. Submittals often show the right CFM at a lower pressure, because pressure drops for economizers, high-efficiency filters, reheat coils or curbs were left out of the selection, or altitude was ignored. Check that the fan selection includes every accessory listed in the model number, at the project’s elevation.

Where it hides
Fan performance table or selection printout
Usual cause
Accessory pressure drops not added to the external static pressure
Found in the field by
Testing, adjusting and balancing under 23 05 93
Fan laws
CFM varies with speed; power with speed cubed

How a selection ends up short

Pressure that goes missing from selections
ItemTypical pressure drop (in. wg)Why it is missed
Economizer and outdoor air hood0.05 to 0.15Selected as a base unit, accessory added later
Upgrade from 2 in. to 4 in. MERV 13 filters0.10 to 0.30Filter option changed after the fan selection
Hot gas reheat coil0.05 to 0.15Dehumidification option not in the selection
Electric or hot water heat section0.05 to 0.20Heat added from a separate table
Wet cooling coil instead of dry0.05 to 0.15Selection run with a dry coil
Supply or return curb transitions0.05 to 0.20Curb furnished by others
Ranges are typical orders of magnitude for packaged equipment; use the manufacturer’s accessory pressure drop table for the model submitted.

Altitude is the other trap. Fans move the same volume of air at altitude but generate less pressure, because the air is less dense. At 5,000 ft, air density is about 83 percent of sea level, so a fan selected at sea level for 1.0 in. wg delivers the scheduled airflow against only about 0.83 in. wg of standard-air resistance. Manufacturers correct for this when the elevation is entered; check that it was.

What the shortfall costs once installed

Fan laws say airflow varies with fan speed, static pressure with speed squared, and power with speed cubed. Recovering a shortfall by speeding up the fan costs much more power than the airflow gained.

Worked example: recovering 9 percent airflow
Delivered at 1.0 in. wg
7,300 CFM
Scheduled
8,000 CFM
Speed increase needed
8,000 ÷ 7,300 = 1.096, about 10 percent
Power increase
1.096³ = 1.32, about 32 percent more
Motor at 4.2 BHP before
About 5.5 BHP after, above a 5 HP motor

On a belt drive this means new sheaves and possibly a larger motor, which in turn changes the MCA, MOP and breaker. On a direct-drive fan, speed may already be at its maximum.

How to check airflow on a submittal

  1. Read the scheduled airflow and external static pressure

    Note whether the schedule’s static is external to the unit or total, and whether it says accessories are included.

  2. Decode the options in the model number

    List every factory option that sits in the airstream: economizer, filters, coils, heat, sound attenuation.

  3. Check the selection includes them

    A selection printout normally lists the accessory pressure drops it added. If it does not, add them from the manufacturer’s table and read the fan table at the new total.

  4. Check elevation

    Confirm the printout states the site elevation, or that the schedule already gives static at site conditions.

  5. Check motor and drive

    The motor horsepower must cover the BHP at the corrected operating point, and belt drives need a sheave selection for the final speed.

Example review comment
RTU-6: Fan selection on page 5 shows 8,000 CFM at 0.6 in. wg ESP and does not include the economizer, MERV 13 filters or reheat coil in the model number. Provide a selection at 1.0 in. wg ESP with all listed accessories at 5,200 ft elevation, with motor BHP and drive.

Belt drives, direct drives and fan arrays

How much margin a fan has depends on its drive. Belt-driven fans can be sped up by changing sheaves, within the fan’s class and the motor’s horsepower. Direct-drive fans with electronically commutated or VFD-driven motors are adjusted by speed setting, but only up to the motor’s maximum speed, and many packaged units ship near it. Fan arrays have no belts but each motor has its own limit.

Where the margin comes from
DriveHow airflow is raisedLimit
Belt driveNew sheaves for higher speedFan class maximum speed, motor horsepower
Direct drive, ECM or VFDHigher speed settingMotor maximum speed, often already close
Fan arrayHigher speed on all fansEach motor’s maximum speed and power
For a direct-drive unit, ask the rep where the selection sits relative to maximum speed. A selection at 95 percent of maximum leaves almost no room for field correction.

Who finds it and who pays

If nobody catches it at submittal, the testing, adjusting and balancing contractor finds it under Section 23 05 93, often weeks before occupancy. The fix is new sheaves or a larger motor and, if the motor grows, a new breaker and wire. Because the equipment was submitted with a selection that did not meet the schedule, the cost usually falls on the contractor who submitted it. The same logic applies to air handlers; see the static pressure build-up on the 23 73 13 page.

Where Cailar fits

What Cailar does

  • Compares airflow and external static pressure on the submittal with the schedule, converting CFM and in. wg in code, and flags a static pressure or airflow below the requirement.
  • Cites the selection page and the schedule cell for each value.

What stays with your reviewer

  • Add accessory pressure drops, correct for altitude or read fan curves.
  • Select fans, sheaves or motors.

Questions and answers

Why does a fan deliver less air than the submittal shows?

Usually because the selection was made at a lower static pressure than the system has, for example without the pressure drops of an economizer, high-efficiency filters or a reheat coil, or without correcting for altitude.

What are the fan laws?

For a given fan and system, airflow varies directly with speed, static pressure with speed squared, and power with speed cubed. A 10 percent speed increase raises power by about 33 percent.

How does altitude affect fan performance?

At altitude the fan moves the same volume of air but develops less pressure, in proportion to air density. At 5,000 ft density is about 83 percent of sea level, so the fan’s pressure capability falls by a similar amount.

Is external static pressure the same as total static pressure?

No. External static pressure is the resistance outside the unit, such as ductwork. Total static adds internal pressure drops such as coils, filters and dampers. Check which one the schedule and the selection use.

Who finds airflow shortfalls?

If missed at submittal, the testing, adjusting and balancing contractor usually finds them during air balance under Section 23 05 93, close to occupancy, when fixes are most expensive.

Sources