Airflow below schedule at the stated static pressure: the shortfall TAB finds too late
Why a unit showing the scheduled CFM can still fall short: accessory static left out, altitude, wet coils, and the fan law cost of fixing it later.
Illustrative example
The short answer
Airflow below schedule means the fan cannot move the scheduled CFM against the scheduled external static pressure once every accessory is in the airstream. Submittals often show the right CFM at a lower pressure, because pressure drops for economizers, high-efficiency filters, reheat coils or curbs were left out of the selection, or altitude was ignored. Check that the fan selection includes every accessory listed in the model number, at the project’s elevation.
- Where it hides
- Fan performance table or selection printout
- Usual cause
- Accessory pressure drops not added to the external static pressure
- Found in the field by
- Testing, adjusting and balancing under 23 05 93
- Fan laws
- CFM varies with speed; power with speed cubed
How a selection ends up short
| Item | Typical pressure drop (in. wg) | Why it is missed |
|---|---|---|
| Economizer and outdoor air hood | 0.05 to 0.15 | Selected as a base unit, accessory added later |
| Upgrade from 2 in. to 4 in. MERV 13 filters | 0.10 to 0.30 | Filter option changed after the fan selection |
| Hot gas reheat coil | 0.05 to 0.15 | Dehumidification option not in the selection |
| Electric or hot water heat section | 0.05 to 0.20 | Heat added from a separate table |
| Wet cooling coil instead of dry | 0.05 to 0.15 | Selection run with a dry coil |
| Supply or return curb transitions | 0.05 to 0.20 | Curb furnished by others |
Altitude is the other trap. Fans move the same volume of air at altitude but generate less pressure, because the air is less dense. At 5,000 ft, air density is about 83 percent of sea level, so a fan selected at sea level for 1.0 in. wg delivers the scheduled airflow against only about 0.83 in. wg of standard-air resistance. Manufacturers correct for this when the elevation is entered; check that it was.
What the shortfall costs once installed
Fan laws say airflow varies with fan speed, static pressure with speed squared, and power with speed cubed. Recovering a shortfall by speeding up the fan costs much more power than the airflow gained.
- Delivered at 1.0 in. wg
- 7,300 CFM
- Scheduled
- 8,000 CFM
- Speed increase needed
- 8,000 ÷ 7,300 = 1.096, about 10 percent
- Power increase
- 1.096³ = 1.32, about 32 percent more
- Motor at 4.2 BHP before
- About 5.5 BHP after, above a 5 HP motor
On a belt drive this means new sheaves and possibly a larger motor, which in turn changes the MCA, MOP and breaker. On a direct-drive fan, speed may already be at its maximum.
How to check airflow on a submittal
Read the scheduled airflow and external static pressure
Note whether the schedule’s static is external to the unit or total, and whether it says accessories are included.
Decode the options in the model number
List every factory option that sits in the airstream: economizer, filters, coils, heat, sound attenuation.
Check the selection includes them
A selection printout normally lists the accessory pressure drops it added. If it does not, add them from the manufacturer’s table and read the fan table at the new total.
Check elevation
Confirm the printout states the site elevation, or that the schedule already gives static at site conditions.
Check motor and drive
The motor horsepower must cover the BHP at the corrected operating point, and belt drives need a sheave selection for the final speed.
RTU-6: Fan selection on page 5 shows 8,000 CFM at 0.6 in. wg ESP and does not include the economizer, MERV 13 filters or reheat coil in the model number. Provide a selection at 1.0 in. wg ESP with all listed accessories at 5,200 ft elevation, with motor BHP and drive.
Belt drives, direct drives and fan arrays
How much margin a fan has depends on its drive. Belt-driven fans can be sped up by changing sheaves, within the fan’s class and the motor’s horsepower. Direct-drive fans with electronically commutated or VFD-driven motors are adjusted by speed setting, but only up to the motor’s maximum speed, and many packaged units ship near it. Fan arrays have no belts but each motor has its own limit.
| Drive | How airflow is raised | Limit |
|---|---|---|
| Belt drive | New sheaves for higher speed | Fan class maximum speed, motor horsepower |
| Direct drive, ECM or VFD | Higher speed setting | Motor maximum speed, often already close |
| Fan array | Higher speed on all fans | Each motor’s maximum speed and power |
Who finds it and who pays
If nobody catches it at submittal, the testing, adjusting and balancing contractor finds it under Section 23 05 93, often weeks before occupancy. The fix is new sheaves or a larger motor and, if the motor grows, a new breaker and wire. Because the equipment was submitted with a selection that did not meet the schedule, the cost usually falls on the contractor who submitted it. The same logic applies to air handlers; see the static pressure build-up on the 23 73 13 page.
Where Cailar fits
What Cailar does
- Compares airflow and external static pressure on the submittal with the schedule, converting CFM and in. wg in code, and flags a static pressure or airflow below the requirement.
- Cites the selection page and the schedule cell for each value.
What stays with your reviewer
- Add accessory pressure drops, correct for altitude or read fan curves.
- Select fans, sheaves or motors.
Questions and answers
Why does a fan deliver less air than the submittal shows?
Usually because the selection was made at a lower static pressure than the system has, for example without the pressure drops of an economizer, high-efficiency filters or a reheat coil, or without correcting for altitude.
What are the fan laws?
For a given fan and system, airflow varies directly with speed, static pressure with speed squared, and power with speed cubed. A 10 percent speed increase raises power by about 33 percent.
How does altitude affect fan performance?
At altitude the fan moves the same volume of air but develops less pressure, in proportion to air density. At 5,000 ft density is about 83 percent of sea level, so the fan’s pressure capability falls by a similar amount.
Is external static pressure the same as total static pressure?
No. External static pressure is the resistance outside the unit, such as ductwork. Total static adds internal pressure drops such as coils, filters and dampers. Check which one the schedule and the selection use.
Who finds airflow shortfalls?
If missed at submittal, the testing, adjusting and balancing contractor usually finds them during air balance under Section 23 05 93, close to occupancy, when fixes are most expensive.
Sources
Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.
- AMCA Publication 201, Fans and Systems
- AHRI 340/360 and AHRI 430 fan rating conditions
- ASHRAE Handbook, Fundamentals, air density and fan laws