Skip to content

Efficiency below the energy code: the wrong metric, the wrong category or the wrong match

How HVAC and plumbing submittals fall below ASHRAE 90.1 or IECC minimums: wrong efficiency metric, wrong size or heating category, unmatched split systems.

Illustration: a split system whose catalog efficiency passes the energy code only with a different indoor coil. The certified rating for the submitted pair falls below the minimum, and the wrong row of the code table was used.

Illustrative example

The short answer

An efficiency below the energy code is equipment whose certified rating is lower than the minimum in the code the project must meet, usually ASHRAE 90.1 or the IECC. The usual causes are the wrong metric, the wrong row of the code table, or a split system rated with a different indoor coil. Check the certified rating for the exact model against the right row of the adopted code.

Codes
ASHRAE 90.1 or IECC as adopted, or a state code such as Title 24
Proof
AHRI or other certified rating for the exact model or matched system
Federal floor
DOE minimums apply even where codes are older
Affects
Permits, energy compliance forms, utility rebates

Use the right metric for the equipment

Efficiency metrics energy codes use
EquipmentMetricsRating standard
Packaged and split AC, 65,000 Btu/h and largerEER and IEERAHRI 340/360
Small AC and heat pumps under 65,000 Btu/hSEER2, EER2, HSPF2 for heat pumpsAHRI 210/240
Heat pump heating, commercial sizesCOP at 47 °F and 17 °FAHRI 340/360
VRF systemsEER, IEER and COPAHRI 1230
Water-cooled and air-cooled chillerskW per ton or EER, plus IPLV, Path A or BAHRI 550/590
Commercial boilersThermal or combustion efficiency by size and fuel10 CFR 431 test methods
Commercial water heatersThermal efficiency and standby loss, or UEF for small units10 CFR 431, 10 CFR 430
FansFan energy index (FEI) in recent editionsAMCA 208
Motors and pumpsNominal full-load efficiency; pump energy index (PEI)NEMA MG 1, DOE rules
Metric names changed in 2023 for small equipment: SEER became SEER2, EER became EER2 and HSPF became HSPF2 under a new test procedure. The numbers are not interchangeable.

Use the right row of the code table

Energy code tables are split by equipment type, size range, and often by heating section type. Reading the wrong row is the most common cause of a false pass or a false fail.

  • Size: ranges such as 65,000 to 135,000 Btu/h and 135,000 to 240,000 Btu/h have different minimums. Use the certified capacity, not the nominal tonnage.
  • Heating section: many tables have separate rows for equipment with electric resistance heat or no heat and for equipment with other heat, such as a gas furnace. The minimums differ.
  • Air-cooled or water-cooled, packaged or split, heat pump or cooling only: each is its own row.
  • Edition: use the edition the jurisdiction adopted, not the latest one. A project permitted under one edition is reviewed under that edition.

Split systems are rated as a matched pair

A split system’s efficiency depends on the outdoor unit and the indoor coil or air handler together. Manufacturers certify specific combinations. Catalogs often print the best combination’s rating beside the outdoor unit. When the submitted indoor unit is a different model, the certified rating of that pair applies, and it can be lower.

  1. List the outdoor and indoor model numbers

    Take both from the submittal, including the coil or air handler and any metering device.

  2. Find the certificate for that pair

    Look up the combination in the AHRI directory, or ask the rep for the certificate. The certificate reference number should be in the submittal.

  3. Compare with the right code row

    Use the certified rating for the pair, at the certified capacity, against the minimum for that size and type.

Example of a false pass

Worked example: the catalog rating versus the certified pair (illustrative values)
Code minimum for the size and type
11.2 EER
Catalog rating printed beside the outdoor unit
11.6 EER, best coil
Indoor coil actually submitted
A smaller coil, to fit the ceiling
Certified rating of the submitted pair
10.9 EER
Result
Below the code minimum by 0.3 EER

Values are illustrative. Always use the certificate for the exact pair and the minimum from the adopted code table.

Example review comment
CU-2 / AHU-2: Submittal shows the outdoor unit’s catalog EER with a different coil. Provide the AHRI certificate for the submitted combination and confirm it meets the minimum in the adopted energy code table for this size and heating type.

Equipment that fails quietly

Energy reviews focus on the big equipment, but several smaller items have their own federal or code minimums that submittals often do not state.

  • Motors: most general-purpose motors from 1 to 500 HP must meet federal efficiency levels; specs usually require NEMA Premium nominal efficiency on the motor data sheet.
  • Dry-type distribution transformers: federal efficiency standards in 10 CFR 431 apply, with levels that tightened in 2016.
  • Fans: recent editions of ASHRAE 90.1 require a minimum fan energy index (FEI) at the design point for many fans of 1 HP and larger, rated under AMCA 208.
  • Clean-water pumps: pumps covered by the federal rule carry a pump energy index (PEI); 1.00 or lower meets the federal minimum.

What it costs when it is missed

  • Energy compliance forms submitted with the permit list the equipment efficiencies; inspectors and plan reviewers check installed equipment against them.
  • Utility incentives often require a minimum efficiency above code, with the certificate as proof. A lower-rated substitute can lose the rebate.
  • Replacing installed equipment for efficiency alone is rare, but the dispute over who pays is common. Catching it at submittal avoids both.

Where Cailar fits

What Cailar does

  • Compares the efficiency stated on the submittal with the value required by the spec or schedule, and flags a value below it with both pages cited.
  • Marks the rating as not stated when the submittal gives no certified figure for the submitted model or pair.

What stays with your reviewer

  • Look up AHRI certificates or select the right row of an energy code table.
  • Prepare energy compliance forms.

Questions and answers

Which energy code applies to HVAC equipment efficiency?

The commercial energy code adopted by the jurisdiction, usually a specific edition of ASHRAE 90.1 or the IECC, or a state code such as California Title 24. Federal DOE minimums also apply to covered equipment regardless of the code.

What is the difference between SEER and SEER2?

SEER2 is measured under a test procedure that took effect in 2023 with higher external static pressure that better reflects real ductwork. SEER2 numbers are lower than SEER for the same equipment, so the two cannot be compared directly.

Why is a split system’s efficiency different from the catalog?

Split systems are certified as matched combinations of outdoor unit and indoor coil or air handler. The catalog often shows the best combination. The certificate for the submitted combination is the one that counts.

What is IEER?

Integrated energy efficiency ratio. AHRI 340/360 combines part-load efficiencies measured at four load points into one number that better reflects how commercial unitary equipment runs. Energy codes set minimum IEER as well as full-load EER.

Does the heating type change the cooling efficiency minimum?

Often, yes. Many code tables have separate rows for equipment with electric resistance heat or no heat and for equipment with other heating sections, such as gas furnaces, with different minimums.

Sources

Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.

Bring us one submittal.

Send us one submittal and its spec section. We run the review with you, and you keep the report.

Run a pilot