Section 22 11 19 Domestic Water Piping Specialties: backflow, mixing valves and the listings that matter

The ASSE listings, lead-free certifications and pressure losses to check on backflow preventers, mixing valves and water hammer arresters under 22 11 19.

Illustration: a reduced pressure backflow preventer submittal. The type, listing and size match, but the pressure loss at design flow is higher than the plumbing calculation allowed and the local approval is not shown.

Illustrative example

The short answer

Section 22 11 19 covers the devices installed in domestic water piping: backflow preventers, thermostatic mixing valves, water hammer arresters, pressure-reducing valves, strainers, hose bibbs and wall hydrants. For each one the submittal must show the right ASSE listing for the application, NSF 61 and NSF 372 lead-free certification, the size and pressure loss at design flow, and, for backflow devices, approval by the local water authority.

MasterFormat division
22, Plumbing
Key listings
ASSE 1013, 1015, 1017, 1070, 1010 and others by device
Lead-free proof
NSF 372 (lead content) and NSF 61 (drinking water contact)
Coordinate with
22 11 16 piping, 22 11 23 pumps, 22 33 00 and 22 34 00 water heaters

What is in Section 22 11 19

Piping specialties are small items with large consequences. A backflow preventer protects the public water supply, a master mixing valve keeps building occupants from scalding, and the pressure each device takes out of the system decides whether the fixtures at the top floor get enough flow. Most of these devices are chosen by listing and size, and most rejections come from one of the two being wrong.

Devices and the standard each must be listed to
DeviceTypical applicationListing to look for
Reduced pressure principle assembly (RP, RPZ)Building service, high-hazard connectionsASSE 1013
Double check valve assemblyLow-hazard connections, some fire servicesASSE 1015
Pressure vacuum breakerIrrigation, process connections above outletASSE 1020
Hose connection vacuum breakerHose bibbs and service sinksASSE 1011
Master thermostatic mixing valveTempered water distribution from the heaterASSE 1017
Point-of-use mixing valveLavatories and sinksASSE 1070
Individual shower valveShowers and tub-showersASSE 1016
Water hammer arresterQuick-closing valves, fixture batteriesASSE 1010, sized by PDI-WH 201 symbol A to F
Pressure-reducing valveZones above the allowed static pressureASSE 1003
Freezeless wall hydrantExterior hose connectionsASSE 1019
Trap seal primerFloor drainsASSE 1018 or 1044
Listing numbers are the American Society of Sanitary Engineering standards most codes reference. Check the plumbing code your jurisdiction adopted for the exact list.

Lead-free certification

Under the federal Safe Drinking Water Act, products that carry water for human consumption must be lead-free: no more than 0.25 percent lead by weighted average across wetted surfaces. The submittal proves it with certification to NSF/ANSI/CAN 372. Most specifications and codes also require NSF/ANSI/CAN 61 for drinking water system components, which covers what else the product can leach into the water.

  • Check the certification covers the exact model and size, not only the product family.
  • Watch for “for non-potable use” versions of the same valve; they look identical on a cut sheet.
  • Brass and bronze bodies are where lead-free versions differ; stainless steel and plastic bodies still need the certification.

Backflow preventers: what the submittal must show

  1. Device type for the hazard

    The type is chosen by the hazard and the code, not by the rep. A double check where the drawings show a reduced pressure assembly is a downgrade in protection and a rejection.

  2. Local approval

    Many water authorities accept only assemblies on an approved list, often the University of Southern California Foundation for Cross-Connection Control and Hydraulic Research list, or the authority’s own. Include the approval for the exact model, size and orientation.

  3. Orientation

    Approvals are often limited to horizontal, vertical-up or vertical-down installation. If the drawings show the assembly vertical, the approval must cover vertical.

  4. Pressure loss at design flow

    Read the flow curve at the scheduled flow and compare it with the allowance in the plumbing calculations. Reduced pressure assemblies commonly lose 10 psi or more at rated flow, which matters when available pressure is tight.

  5. Relief discharge and drain

    A reduced pressure assembly discharges water through its relief port during operation and testing. The submittal should include the air gap fitting, and the drawings must show a drain sized for the relief flow.

Worked example: does the building still get enough pressure?
Minimum street pressure
62 psi
Meter and service piping loss
6 psi
Backflow preventer at 250 GPM
13 psi
Static lift to top fixture (60 ft × 0.433)
26 psi
Piping friction to top fixture
8 psi
Left at the top fixture
9 psi

A flush valve that needs 25 psi will not work. With the 10 psi the calculation assumed, 12 psi was already marginal; this is why the backflow pressure loss belongs in the review, not only the size.

Thermostatic mixing valves

Mixing valves are often rejected because the listing does not match the job. A master valve for a whole building’s tempered water loop is listed to ASSE 1017 and is not a point-of-use scald guard; a lavatory valve is ASSE 1070. Then the sizing: a master valve has a minimum flow below which it cannot hold temperature, and recirculation flow alone is often below it.

Mixing valve values to check
ValueWhere it comes fromCommon problem
ListingSpec and codeASSE 1017 submitted where 1070 is required, or the reverse
Design flow and pressure lossScheduleLoss at design flow above the plumbing calculation
Minimum flowValve dataRecirculation flow alone is below the valve minimum, so the loop drifts
Outlet temperature rangeScheduleRange does not reach the required setpoint
Recirculation arrangementDrawingsNo bypass or low-flow valve where the drawings call for one
Lead-free certificationSpecNot stated for the model

Why piping specialty submittals come back

Common rejection reasons
ReasonHow to avoid it
Backflow device not on the local approval listCheck the authority’s list for the model, size and orientation
Wrong ASSE listing for the applicationMatch each device to the listing in the table above
No lead-free certificationInclude NSF 372 and NSF 61 for each model
Pressure loss not shown at design flowMark the design flow on the flow curve
Water hammer arresters not sizedSize by fixture units to PDI-WH 201 and list the size per location
Product line data with nothing markedMark the size and options for each tag

Where Cailar fits

What Cailar does

  • Lists the listings, sizes and pressure limits found in Section 22 11 19 and the schedule, each with its page, for a reviewer to confirm.
  • Compares the submitted pressure loss and size with the requirement in code and flags a value that exceeds it, citing both pages.
  • Marks a certification or approval as not stated when the submittal has no page for it.

What stays with your reviewer

  • Check a water authority’s approval list or confirm a certification on the certifier’s website.
  • Run the plumbing pressure calculation.

Questions and answers

What does Section 22 11 19 cover?

Domestic water piping specialties: backflow preventers, vacuum breakers, thermostatic mixing valves, water hammer arresters, pressure-reducing valves, strainers, hose bibbs, wall hydrants and trap primers installed in the domestic water system.

What is the difference between ASSE 1017 and ASSE 1070?

ASSE 1017 covers master temperature-actuated mixing valves that supply tempered water to a distribution system. ASSE 1070 covers point-of-use valves that limit the temperature at a fixture such as a lavatory. They are not interchangeable.

How do I prove a valve is lead-free?

Include certification to NSF/ANSI/CAN 372 for the exact model, which shows the wetted surfaces contain no more than 0.25 percent lead by weighted average. Most projects also require NSF/ANSI/CAN 61 for drinking water components.

Why does the backflow preventer need local approval?

The water authority is responsible for protecting the public supply and many accept only assemblies on an approved list for a given size and orientation. An unlisted assembly can fail its first test or inspection even if the engineer approved the submittal.

How much pressure does a reduced pressure backflow preventer lose?

It depends on the model, size and flow. Many lose around 10 psi or more at rated flow. Read the manufacturer’s flow curve at the scheduled flow and compare it with the allowance in the plumbing calculations.

Sources

Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.

Bring us one submittal.

Send us one submittal and its spec section. We run the review with you, and you keep the report.

Run a pilot