Section 22 11 19 Domestic Water Piping Specialties: backflow, mixing valves and the listings that matter
The ASSE listings, lead-free certifications and pressure losses to check on backflow preventers, mixing valves and water hammer arresters under 22 11 19.
Illustrative example
The short answer
Section 22 11 19 covers the devices installed in domestic water piping: backflow preventers, thermostatic mixing valves, water hammer arresters, pressure-reducing valves, strainers, hose bibbs and wall hydrants. For each one the submittal must show the right ASSE listing for the application, NSF 61 and NSF 372 lead-free certification, the size and pressure loss at design flow, and, for backflow devices, approval by the local water authority.
- MasterFormat division
- 22, Plumbing
- Key listings
- ASSE 1013, 1015, 1017, 1070, 1010 and others by device
- Lead-free proof
- NSF 372 (lead content) and NSF 61 (drinking water contact)
- Coordinate with
- 22 11 16 piping, 22 11 23 pumps, 22 33 00 and 22 34 00 water heaters
What is in Section 22 11 19
Piping specialties are small items with large consequences. A backflow preventer protects the public water supply, a master mixing valve keeps building occupants from scalding, and the pressure each device takes out of the system decides whether the fixtures at the top floor get enough flow. Most of these devices are chosen by listing and size, and most rejections come from one of the two being wrong.
| Device | Typical application | Listing to look for |
|---|---|---|
| Reduced pressure principle assembly (RP, RPZ) | Building service, high-hazard connections | ASSE 1013 |
| Double check valve assembly | Low-hazard connections, some fire services | ASSE 1015 |
| Pressure vacuum breaker | Irrigation, process connections above outlet | ASSE 1020 |
| Hose connection vacuum breaker | Hose bibbs and service sinks | ASSE 1011 |
| Master thermostatic mixing valve | Tempered water distribution from the heater | ASSE 1017 |
| Point-of-use mixing valve | Lavatories and sinks | ASSE 1070 |
| Individual shower valve | Showers and tub-showers | ASSE 1016 |
| Water hammer arrester | Quick-closing valves, fixture batteries | ASSE 1010, sized by PDI-WH 201 symbol A to F |
| Pressure-reducing valve | Zones above the allowed static pressure | ASSE 1003 |
| Freezeless wall hydrant | Exterior hose connections | ASSE 1019 |
| Trap seal primer | Floor drains | ASSE 1018 or 1044 |
Lead-free certification
Under the federal Safe Drinking Water Act, products that carry water for human consumption must be lead-free: no more than 0.25 percent lead by weighted average across wetted surfaces. The submittal proves it with certification to NSF/ANSI/CAN 372. Most specifications and codes also require NSF/ANSI/CAN 61 for drinking water system components, which covers what else the product can leach into the water.
- Check the certification covers the exact model and size, not only the product family.
- Watch for “for non-potable use” versions of the same valve; they look identical on a cut sheet.
- Brass and bronze bodies are where lead-free versions differ; stainless steel and plastic bodies still need the certification.
Backflow preventers: what the submittal must show
Device type for the hazard
The type is chosen by the hazard and the code, not by the rep. A double check where the drawings show a reduced pressure assembly is a downgrade in protection and a rejection.
Local approval
Many water authorities accept only assemblies on an approved list, often the University of Southern California Foundation for Cross-Connection Control and Hydraulic Research list, or the authority’s own. Include the approval for the exact model, size and orientation.
Orientation
Approvals are often limited to horizontal, vertical-up or vertical-down installation. If the drawings show the assembly vertical, the approval must cover vertical.
Pressure loss at design flow
Read the flow curve at the scheduled flow and compare it with the allowance in the plumbing calculations. Reduced pressure assemblies commonly lose 10 psi or more at rated flow, which matters when available pressure is tight.
Relief discharge and drain
A reduced pressure assembly discharges water through its relief port during operation and testing. The submittal should include the air gap fitting, and the drawings must show a drain sized for the relief flow.
- Minimum street pressure
- 62 psi
- Meter and service piping loss
- 6 psi
- Backflow preventer at 250 GPM
- 13 psi
- Static lift to top fixture (60 ft × 0.433)
- 26 psi
- Piping friction to top fixture
- 8 psi
- Left at the top fixture
- 9 psi
A flush valve that needs 25 psi will not work. With the 10 psi the calculation assumed, 12 psi was already marginal; this is why the backflow pressure loss belongs in the review, not only the size.
Thermostatic mixing valves
Mixing valves are often rejected because the listing does not match the job. A master valve for a whole building’s tempered water loop is listed to ASSE 1017 and is not a point-of-use scald guard; a lavatory valve is ASSE 1070. Then the sizing: a master valve has a minimum flow below which it cannot hold temperature, and recirculation flow alone is often below it.
| Value | Where it comes from | Common problem |
|---|---|---|
| Listing | Spec and code | ASSE 1017 submitted where 1070 is required, or the reverse |
| Design flow and pressure loss | Schedule | Loss at design flow above the plumbing calculation |
| Minimum flow | Valve data | Recirculation flow alone is below the valve minimum, so the loop drifts |
| Outlet temperature range | Schedule | Range does not reach the required setpoint |
| Recirculation arrangement | Drawings | No bypass or low-flow valve where the drawings call for one |
| Lead-free certification | Spec | Not stated for the model |
Why piping specialty submittals come back
| Reason | How to avoid it |
|---|---|
| Backflow device not on the local approval list | Check the authority’s list for the model, size and orientation |
| Wrong ASSE listing for the application | Match each device to the listing in the table above |
| No lead-free certification | Include NSF 372 and NSF 61 for each model |
| Pressure loss not shown at design flow | Mark the design flow on the flow curve |
| Water hammer arresters not sized | Size by fixture units to PDI-WH 201 and list the size per location |
| Product line data with nothing marked | Mark the size and options for each tag |
Where Cailar fits
What Cailar does
- Lists the listings, sizes and pressure limits found in Section 22 11 19 and the schedule, each with its page, for a reviewer to confirm.
- Compares the submitted pressure loss and size with the requirement in code and flags a value that exceeds it, citing both pages.
- Marks a certification or approval as not stated when the submittal has no page for it.
What stays with your reviewer
- Check a water authority’s approval list or confirm a certification on the certifier’s website.
- Run the plumbing pressure calculation.
Questions and answers
What does Section 22 11 19 cover?
Domestic water piping specialties: backflow preventers, vacuum breakers, thermostatic mixing valves, water hammer arresters, pressure-reducing valves, strainers, hose bibbs, wall hydrants and trap primers installed in the domestic water system.
What is the difference between ASSE 1017 and ASSE 1070?
ASSE 1017 covers master temperature-actuated mixing valves that supply tempered water to a distribution system. ASSE 1070 covers point-of-use valves that limit the temperature at a fixture such as a lavatory. They are not interchangeable.
How do I prove a valve is lead-free?
Include certification to NSF/ANSI/CAN 372 for the exact model, which shows the wetted surfaces contain no more than 0.25 percent lead by weighted average. Most projects also require NSF/ANSI/CAN 61 for drinking water components.
Why does the backflow preventer need local approval?
The water authority is responsible for protecting the public supply and many accept only assemblies on an approved list for a given size and orientation. An unlisted assembly can fail its first test or inspection even if the engineer approved the submittal.
How much pressure does a reduced pressure backflow preventer lose?
It depends on the model, size and flow. Many lose around 10 psi or more at rated flow. Read the manufacturer’s flow curve at the scheduled flow and compare it with the allowance in the plumbing calculations.
Sources
Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.
- ASSE International product standards (1003, 1010, 1011, 1013, 1015, 1016, 1017, 1019, 1020, 1070)
- NSF/ANSI/CAN 61 and NSF/ANSI/CAN 372
- Safe Drinking Water Act, Section 1417, as amended by the Reduction of Lead in Drinking Water Act
- PDI-WH 201, Water Hammer Arresters