Section 22 34 00 Fuel-Fired Domestic Water Heaters: input, recovery and venting checks

How to check a gas water heater submittal under 22 34 00: input, efficiency, recovery at the design rise, ASME limits, venting category and gas pressure.

Illustration: a condensing gas water heater submittal. Input, storage and recovery match the schedule, but the heater needs more gas pressure than the gas piping design provides and the vent length is not stated.

Illustrative example

The short answer

Section 22 34 00 covers gas-fired and oil-fired water heaters for domestic hot water. Check the submittal for the scheduled input and storage, the recovery rate at the design temperature rise, the efficiency rating the energy code requires, whether ASME construction is needed, the vent category and allowed vent length, and the minimum gas inlet pressure against the gas piping design.

MasterFormat division
22, Plumbing
Efficiency rating
Thermal efficiency for commercial units, UEF for residential-duty units
ASME threshold
Above 200,000 Btu/h input, 210 °F or 120 gallons in most codes
Coordinate with
23 11 23 gas piping, 22 11 19 mixing valves, Division 26 power

What Section 22 34 00 covers

The section covers fuel-fired heaters for domestic hot water: commercial gas storage heaters, condensing storage heaters, instantaneous (tankless) units and volume water heaters that pair a heater with separate storage tanks. Electric heaters are in 22 33 00. Heaters that serve space heating belong in Division 23, although some buildings use one heater for both and the spec says so.

Heater types and their usual weak spot on submittals
TypeTypical useWhat to watch
Atmospheric or power-vent storageOlder or smaller commercial systemsEfficiency below current energy code minimums
Condensing storageMost new commercial projectsVent material, condensate drain, 120 V power
Instantaneous, single or rackedRestaurants, small buildings, point loadsFlow at the design rise, gas demand when all units fire
Volume heater with tanksLarge loadsTwo submittals: heater and tanks must match the piping diagram

Recovery at the design temperature rise

Recovery is the number of gallons per hour the heater can raise through a given temperature rise. Manufacturers publish recovery tables for several rises; the schedule should state the rise, usually from the coldest incoming water to the storage setpoint. Check the submitted recovery at that rise, not at the friendlier 40 or 60 °F rise often printed first.

Worked example: recovery for a 199,999 Btu/h condensing heater
Input
199,999 Btu/h
Thermal efficiency
95 percent
Heat into the water
199,999 × 0.95 = 190,000 Btu/h
Design rise
50 °F incoming to 140 °F storage = 90 °F
Recovery
190,000 ÷ (8.25 × 90) = 256 GPH

8.25 is the weight of a gallon of water in pounds times its specific heat of one Btu per pound per degree. The same heater recovers about 576 GPH at a 40 °F rise, which is why the rise must be stated.

Efficiency, ratings and ASME construction

  • Commercial gas storage heaters are rated in thermal efficiency and standby loss under 10 CFR 431. Residential-duty units of 75,000 Btu/h or less are rated in uniform energy factor (UEF). Make sure the submittal gives the rating the energy code table uses for that size.
  • Federal minimums and energy code tables change. The U.S. Department of Energy has adopted stricter standards for commercial gas water heaters; check the compliance date against the project’s manufacture and installation dates.
  • Most mechanical and plumbing codes require ASME construction for water heaters above 200,000 Btu/h input, 210 °F water temperature or 120 gallons nominal capacity. A 199,999 Btu/h rating is common for that reason. If the schedule calls for 250,000 Btu/h, the submittal needs the ASME data report or stamp.
  • Air quality districts may set NOx limits, such as low-NOx requirements in parts of California. If the spec cites one, the submittal must show the certification.

Venting, gas pressure and power

  1. Vent category and material

    Condensing heaters run Category IV vents under positive pressure with acidic condensate. The listed vent materials are named in the installation manual, often PVC, CPVC, polypropylene or stainless steel. Ask for the manual page, because the listing comes from it.

  2. Vent length

    Each heater has a maximum equivalent vent length, with deductions for every elbow. Measure the run on the plans and compare. A rooftop termination five floors up can exceed the limit.

  3. Minimum gas inlet pressure

    The heater lists a minimum and maximum inlet gas pressure. Compare the minimum with the pressure the gas piping design delivers at the heater with all appliances running, from Section 23 11 23 and the gas riser diagram.

  4. Condensate

    Condensing units need a condensate drain and usually a neutralizer. Both should be in the submittal or in the piping specialties.

  5. Electrical

    Condensing and power-vent heaters need a 120 V circuit. Confirm it is on the electrical drawings and that the heater’s amperage is listed.

Why water heater submittals are returned

Common rejection reasons
ReasonHow to avoid it
Recovery shown at a lower rise than scheduledQuote the recovery at the scheduled rise
Efficiency rating below the energy codeCheck the code table for the heater size and fuel
Input above 200,000 Btu/h without ASME dataInclude the ASME data report, or reselect
Vent length exceeds the maximumMeasure the run and include the manufacturer’s vent table
Gas inlet pressure requirement not metCompare with the gas design and raise an RFI early
Tempering valve missing or wrong listingCoordinate with 22 11 19 for the ASSE 1017 valve

Where Cailar fits

What Cailar does

  • Reads input, storage, recovery and efficiency from the submittal and compares each with the schedule and spec, with pages cited.
  • Converts units in code, so an input given in MBH is compared with a schedule in Btu/h without retyping.
  • Marks vent length or gas pressure as not stated when the submittal has no value.

What stays with your reviewer

  • Calculate recovery, vent equivalent length or gas pipe sizing for you.
  • Decide whether a derated or reselected heater is acceptable. The engineer does.

Questions and answers

How do I calculate water heater recovery?

Divide the heat delivered to the water by 8.25 times the temperature rise. Heat delivered is the input in Btu/h times the thermal efficiency. A 199,999 Btu/h heater at 95 percent efficiency recovers about 256 gallons per hour at a 90 °F rise.

When does a water heater need ASME construction?

Most U.S. mechanical and plumbing codes require ASME construction when the heater exceeds 200,000 Btu/h input, 210 °F water temperature or 120 gallons nominal capacity. Check the code adopted for the project.

What efficiency rating should a commercial gas water heater show?

Commercial gas storage heaters are rated in thermal efficiency and standby loss. Residential-duty heaters of 75,000 Btu/h or less are rated in uniform energy factor. Use the rating the project’s energy code table lists for that size.

Why does the gas inlet pressure matter on a submittal?

Each heater needs a minimum gas pressure at its inlet to reach full input. If the gas piping design delivers less with all appliances running, the heater derates or locks out. Compare the heater’s minimum with the design pressure at the heater.

Are electric water heaters in Section 22 34 00?

No. Electric domestic water heaters are in Section 22 33 00. Section 22 34 00 covers fuel-fired heaters, mainly gas.

Sources

Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.

  • 10 CFR 431 Subpart G, commercial water heater energy conservation standards
  • ANSI Z21.10.3/CSA 4.3, gas-fired water heaters above 75,000 Btu/h
  • ASME Boiler and Pressure Vessel Code, Section IV
  • International Mechanical Code and International Plumbing Code, water heater provisions