Section 23 52 16 Condensing Boilers: efficiency at return temperature, turndown and flow
Reviewing a condensing boiler submittal: efficiency at the real return water temperature, turndown, minimum flow, venting, CSD-1 and gas pressure.
Illustrative example
The short answer
Section 23 52 16 covers condensing boilers for hydronic heating. Check that the submittal shows input and output at the scheduled conditions, efficiency at the design return water temperature rather than only the peak rating, turndown low enough for the building’s smallest load, the boiler’s minimum flow and maximum temperature rise against the piping design, and the venting, gas pressure, condensate and control requirements.
- MasterFormat division
- 23, HVAC
- Condensing happens
- When return water is below the flue gas dew point, roughly 130 °F for natural gas
- Safety controls
- ASME CSD-1 on most commercial boilers up to 12.5 million Btu/h input
- Coordinate with
- 23 21 13 and 23 21 23 piping and pumps, 23 11 23 gas, 23 09 23 controls
What Section 23 52 16 covers
Condensing boilers recover the latent heat in flue gas by cooling it below its dew point, which only happens when the water returning to the boiler is cool enough. Their efficiency depends on the system as much as on the boiler. That is why a condensing boiler submittal has to be read against the heating water temperatures, the piping arrangement and the controls, not only against its rating plate. Non-condensing boilers are usually in 23 52 33 or similar sections.
Efficiency depends on return water temperature
Brochures quote peak efficiency at low return water temperature, often 95 percent or more. At a 160 °F return, the same boiler barely condenses. Ask for the manufacturer’s efficiency curve and read it at the schedule’s design return temperature, and at the lower return temperatures the reset schedule reaches in mild weather.
| Return water temperature | Typical thermal efficiency | What is happening |
|---|---|---|
| 80 °F | About 97 percent | Strong condensing |
| 110 °F | About 94 percent | Condensing |
| 130 °F | About 89 percent | Near the dew point |
| 160 °F | About 86 percent | Not condensing |
Turndown and the smallest load
Turndown is the ratio of maximum to minimum firing rate. A boiler that cannot fire low enough short-cycles at light load, which wastes energy and wears the ignition system.
- Boiler input
- 2,000 MBH
- Minimum firing at 10:1
- 200 MBH
- Smallest load, summer reheat
- 150 MBH
- Minimum firing at 20:1
- 100 MBH
- Result
- 10:1 cycles on and off all summer; 20:1 modulates
Multiple smaller boilers can achieve the same result. Turndown is a system property; the spec states what the engineer chose.
Flow, temperature rise and piping
- Minimum flow: many boilers, especially low-mass watertube designs, need a minimum flow through the heat exchanger. Compare it with the lowest flow the heating loop reaches, especially in variable-primary systems.
- Maximum temperature rise: the boiler may limit the difference between supply and return, such as 40 °F or 60 °F. A design with a 40 °F rise on a boiler limited to 30 °F is a mismatch.
- Pressure drop through the boiler at design flow feeds the pump head; see 23 21 23 Hydronic Pumps.
- Primary-secondary or direct piping: the installation manual states what the manufacturer allows. Check it against the piping diagram.
- Maximum working pressure and the ASME Section IV stamp must suit the system pressure.
Input, output, altitude and redundancy
Schedules give either input or output, and the two differ by the efficiency. A boiler with 2,000 MBH input delivers about 1,900 MBH at 95 percent efficiency, and less when it is not condensing. Read which one the schedule names before comparing numbers.
- Altitude: above a certain elevation, often 2,000 ft, burners are derated unless the boiler is certified for high altitude. Projects in Denver or Salt Lake City need the output at the site elevation.
- Redundancy: many designs size the plant so the building can be heated with one boiler out of service, called N+1. Check the number of boilers and each one’s output against that intent, which is usually stated in the schedule notes or the basis of design.
- Space heating plus domestic water: if the boiler also heats domestic water through an indirect tank, the schedule load includes it. The submittal should include the indirect tank or reference its own section.
Venting, gas, condensate and controls
| Item | Check |
|---|---|
| Vent category and material | Category IV, materials listed in the installation manual |
| Vent and combustion air length | Maximum equivalent lengths against the layout |
| Common venting | Allowed only with the manufacturer’s approved common vent system |
| Gas inlet pressure | Minimum and maximum against the gas design at full fire of all appliances |
| Condensate | Neutralizer and drain to a suitable receptor |
| CSD-1 controls | Flame safeguard, limits and low-water cutoff as ASME CSD-1 requires |
| Electrical | Voltage and current for burner, controls and any integral pump |
| Boiler sequencing | Lead-lag control and interface to the building automation system |
| Emissions | NOx certification where an air district rule applies |
Why condensing boiler submittals are returned
| Reason | How to avoid it |
|---|---|
| Only peak efficiency shown | Include the curve and the value at design return temperature |
| Turndown below the spec | Check the ratio for the size submitted, not the product line |
| Minimum flow above the loop’s low-load flow | Check the piping diagram and controls sequence |
| Temperature rise outside the boiler’s limit | Compare the boiler limit with the scheduled supply and return |
| Vent length or material not shown | Include the vent table and installation manual page |
| CSD-1 controls missing | List each required control on the submittal |
Where Cailar fits
What Cailar does
- Compares input, output, turndown and flow from the boiler data with the schedule, with MBH and GPM converted in code.
- Marks efficiency at the design return temperature, or any other required value, as not stated when the submittal leaves it out.
What stays with your reviewer
- Analyze the piping arrangement or controls sequence for flow or cycling problems.
- Read efficiency off a curve or calculate seasonal efficiency.
Questions and answers
At what return water temperature does a boiler condense?
Flue gas from natural gas starts condensing when it is cooled below its dew point, around 130 °F. Return water must be below that for meaningful condensing; efficiency rises as return temperature falls.
What is boiler turndown?
The ratio of maximum to minimum firing rate. A 2,000 MBH boiler with 10:1 turndown fires down to 200 MBH; with 20:1 it fires down to 100 MBH. Higher turndown avoids short-cycling at light loads.
Does a condensing boiler need a minimum flow?
Many do, especially low-mass watertube designs. The installation manual states the minimum flow and maximum temperature rise. The heating system’s piping and controls must keep flow above that minimum.
What is ASME CSD-1?
ASME CSD-1 is the standard for controls and safety devices on automatically fired boilers, typically those up to 12.5 million Btu/h input. It covers flame safeguards, limits and low-water cutoffs. Many jurisdictions require it.
Can condensing boilers share a vent?
Only when the manufacturer allows it and supplies or approves the common vent system, because condensing boilers vent under positive pressure. Otherwise each boiler needs its own vent.
Sources
Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.
- ASME Boiler and Pressure Vessel Code, Section IV, Heating Boilers
- ASME CSD-1, Controls and Safety Devices for Automatically Fired Boilers
- 10 CFR 431 Subpart E, commercial packaged boilers
- ANSI Z21.13/CSA 4.9, gas-fired low pressure steam and hot water boilers