FLA, RLA and LRA: the three motor currents on an equipment nameplate
What full-load amps, rated-load amps and locked-rotor amps mean, which NEC rules use each one, and how they show up on HVAC and pump submittals.
The short answer
FLA, full-load amps, is the current a motor draws at rated horsepower and voltage. RLA, rated-load amps, is the manufacturer’s rated running current for a hermetic refrigerant compressor. LRA, locked-rotor amps, is the current at the instant of starting, often five to eight times the running current. Conductors and breakers for general motors are sized from NEC table currents, overloads from nameplate FLA, and HVAC circuits from the MCA and MOP built on RLA and FLA.
- FLA
- Running current at full load, on the motor nameplate
- RLA
- Rated running current of a hermetic compressor (NEC 440.2)
- LRA
- Starting current with the rotor stopped
- NEC tables
- 430.248 to 430.250 give standard full-load currents by horsepower
Three currents, three uses
| Current | Where it appears | Used for |
|---|---|---|
| FLA (nameplate) | Motor nameplate and motor data sheet | Motor overload protection setting |
| Full-load current (NEC table) | NEC Tables 430.248 to 430.250 | Conductor, disconnect and short-circuit protection sizing for general motors |
| RLA | Compressor nameplate, HVAC electrical data table | MCA and MOP calculations for HVAC equipment |
| LRA | Motor or compressor nameplate | Disconnect sizing for hermetic motors, voltage dip and generator sizing |
The distinction between nameplate FLA and the NEC table current trips up many reviews. NEC 430.6(A)(1) says to use the table values, not the nameplate, when sizing conductors and short-circuit protection for general-purpose motors, and the nameplate FLA when setting overload protection. Packaged HVAC equipment is different again: its circuit is sized from the nameplate MCA and MOP, which the manufacturer calculates from RLA and FLA.
Worked example: a 10 HP pump motor at 460 V
- Nameplate FLA
- 12.6 A
- NEC Table 430.250 full-load current, 10 HP at 460 V
- 14 A
- Branch-circuit conductors at 125 percent of table current
- 17.5 A minimum ampacity
- Overload setting, service factor 1.15, at up to 125 percent of nameplate
- 15.75 A maximum
- If someone used nameplate FLA for the conductors
- 15.75 A, a smaller wire than the code requires
References: NEC 430.6(A), 430.22 and 430.32 (2023 numbering). Premium-efficiency motors often have nameplate FLA well below the table value, which widens the gap between the two numbers.
RLA and hermetic compressors
A hermetic compressor’s motor is sealed inside the refrigerant circuit, so its current depends on refrigerant conditions as well as load. NEC Article 440 defines rated-load current as the value the manufacturer assigns from running the compressor at rated conditions. Some nameplates also show a branch-circuit selection current, which is higher than RLA and, when given, is used instead of RLA for sizing.
- RLA is not the maximum current the compressor can draw. Under high head pressure on a hot day, it can run above RLA until its internal protection trips.
- RLA, not horsepower, drives the HVAC unit’s MCA and MOP. Two units with the same tonnage can have quite different RLA.
- When the compressor or refrigerant changes between submittals, RLA changes, and so do MCA and MOP.
LRA, starting and why it matters
At the instant a motor starts, its rotor is still and it draws locked-rotor current, typically five to eight times its running current for an across-the-line start. That current lasts a fraction of a second to a few seconds, but it sets several design decisions.
| Decision | Why LRA matters |
|---|---|
| Disconnect rating for hermetic motors | NEC 440.12 converts RLA and LRA into an equivalent horsepower for the disconnect |
| Generator sizing | Starting the largest motor causes the biggest voltage dip |
| Voltage dip on weak services | Lights flicker and contactors drop out when a large compressor starts |
| Choice of starter | Soft starters and drives limit starting current |
Reading an HVAC electrical data table
Packaged HVAC submittals usually present motor currents in one table per voltage. A typical row lists each compressor’s RLA and LRA, each fan motor’s FLA and horsepower, and the unit’s MCA and MOP. Read across the row for the voltage supplied and the options ordered, because electric heat, powered exhaust or a high-static fan motor each have their own rows or adders.
| Component | Quantity | RLA or FLA (A) | LRA (A) |
|---|---|---|---|
| Compressor | 2 | 8.0 RLA each | 55 each |
| Condenser fan motor | 2 | 0.9 FLA each | |
| Supply fan motor, 3 HP | 1 | 4.8 FLA | |
| Unit MCA and MOP | MCA 22.6 A, MOP 30 A |
What to check on a submittal
- The current values are for the voltage being supplied; FLA at 208 V is higher than at 230 V. See voltage mismatches.
- Motor data includes nameplate FLA, service factor and efficiency for every scheduled motor.
- Compressor data includes RLA and LRA, or the unit’s MCA and MOP for packaged equipment.
- Drives are sized from nameplate FLA, not horsepower; see the 26 29 23 VFD page.
- Generator sizing reports use the LRA or code letter of the largest motors that start on generator power.
Where Cailar fits
What Cailar does
- Reads current values in amps from submittal data tables and compares them with the requirement, with the page cited.
- Uses the nameplate MCA and MOP, not FLA, when checking HVAC breakers a reviewer enters from the panel schedule.
What stays with your reviewer
- Look up NEC table currents or size conductors and overloads.
- Calculate starting current or voltage dip.
Questions and answers
What is the difference between FLA and RLA?
FLA, full-load amps, is the running current of a general motor at rated horsepower. RLA, rated-load amps, is the manufacturer’s rated running current for a hermetic refrigerant compressor, whose load depends on refrigerant conditions.
Should I size wire from nameplate FLA?
For general-purpose motors, no. NEC 430.6(A)(1) requires the full-load currents in Tables 430.248 to 430.250 for sizing conductors and short-circuit protection. Nameplate FLA is used for overload protection. HVAC equipment circuits are sized from the nameplate MCA and MOP.
How much higher is LRA than running current?
Typically five to eight times the running current for a motor started across the line. Soft starters and variable-frequency drives reduce it.
What is branch-circuit selection current?
A value some compressor nameplates show that is higher than RLA. When it is marked, NEC Article 440 uses it instead of RLA for sizing the branch circuit and its protection.
Does FLA change with voltage?
Yes. For the same power, current rises as voltage falls, so a motor’s FLA at 208 V is higher than at 230 V or 460 V. Use the values for the voltage actually supplied.
Sources
Standards and codes this page relies on. Check the edition your project and jurisdiction have adopted.
- NFPA 70, National Electrical Code, Articles 430 and 440 (2023 numbering)
- NEMA MG 1, Motors and Generators, nameplate marking and code letters